See Table 4, Temperature/Ohm Relationship, for valid temperature
range when connected to an outside air thermistor.
Table 4 — Temperature/Ohm Relationship
TEMP (°F/°C)
OHMS
30/—-1
34,480
32/0
32,630
34/1
30,760
36/2
29,220
38/4
27,470
40/5
26,020
42/6
24,680
44/7
23,320
46/8
22,070
48/9
20,910
50/10
19,830
52/11
18,820
54/12
17,870
>
56/14
16,920
os
58/15
16,160
60/16
15,260
62/17
14,530
64/18
13,790
66/19
13,090
68/20
12,480
70/21
11,860
72/22
11,270
74/24
10,750
76/25
10,250
78/26
9,750
80/27
9,300
82/28
8,840
84/29
8,432
86/30
8,042
88/31
7,668
90/32
7,310
92/33
6,993
94/34
6,661
96/35
6,368
98/36
6,085
100/38
5,811
102/39
5,571
104/40
5,313
106/41
5,088
108/42
4,869
110/43
4,660
112/44
4,450
114/46
4,268
116/47
4,019
118/48
3,918
120/49
3,750
©2011 CAC / BDP ® 7310 W. Morris St. @ Indianapolis, IN 46234
These
products
earned
the
ENERGY STAR® by meeting strict
energy efficiency guidelines set by
Natural Resources Canada and
the US EPA. They meet ENERGY
STAR
requirements
only
when
SS eene iyi
used in Canada.
Edition Date:
05/11
Catalog No:
IM—HRV-01
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
16
Replaces: NEW

Advertisement

Table of Contents
loading

Table of Contents