Maintains a constant flow of fluid through the heater tank to prevent damage to the heating
elements and fluid
•
Factory pre-set to maintain the system pressure specified by the customer- must not be
tampered with in any way
Pressure Switch
•
Built into each unit
•
Guards against heater damage
•
Prevents the heater elements from being energized unless the pump is running and fluid is
in the system
•
Factory set; no field adjustments needed - must not be tampered with
Safety Thermostat
•
Protects against thermal runaway
•
Shuts down the heater outputs, sounds the audible alarm, and lights the alarm indicator if an
over temperature condition exists
•
Pump continues to run, pumping fluid through the system to prevent heater damage
•
Automatic reset design resets the thermostat as the unit cools
•
All heater controller functions lock out until you reset main power
Note:
Always have a qualified maintenance technician determine and correct the cause of an
over temperature fault before you resume operation
Electrical Components
•
NEMA 1 standard electrical enclosure
•
IEC motor starters
•
Full unit fusing - pump motor, heater, primary side transformer
•
High temperature heater cutout
•
High temperature audible and visual alarm, activated by the safety thermostat
•
Pressure switch shuts down heater for low pressure
•
Mercury heater contactors
•
Pump motor and immersion heater operate on three-phase, 50/60 cycle nominal voltage
with control circuit at I l 5V single phase
•
Single phase machine tool transformer with primary fuse protection and grounded
secondary supplies control circuit voltage
•
•
Electrical panel complies with NEC provisions