Sinclair SDV6 User And Installation Manual page 50

Commercial air conditioners
Hide thumbs Also See for SDV6:
Table of Contents

Advertisement

RS-485 (P Q) communication wiring configuration
L1+La+Ln≤1200m. Communication wiring 2*0.75mm
N L
Breaker
Master ODU
1# IDU
Q
Q L
P
P
L1
RS-485 (P Q E) communication wiring configuration
L1+La+Ln≤1200m.
Communication wiring 3*0.75mm
N L
Breaker
Master ODU
1# IDU
P Q
E
P Q
L1
CAUTION
After the last indoor unit, the communication
wiring should not route back to the outdoor
unit as this will form a closed loop.
In the last indoor unit, connect a resistor of
120 ohms between the P and Q terminals.
Do not bind the communication line,
refrigerant piping and power cable together.
When the power cable and communication
line are laid in parallel, the distance between
the two lines must be 5cm or more to
prevent signal source interference.
All IDUs in a system must be powered
through a uniform power supply so that they
can be powered on or off at the same time.
All communication lines of the IDUs and
ODUs must be connected in a series, use
the shielded wire, and the shield layer must
be grounded.
The communication wiring (P, Q, E) must
through the magnetic ring from the main
board to the IDUs.
2
Distribution box
···
2-(n-2)# IDU
N
La
2
Distribution box
···
2-(n-2)# IDU
E
L
N
La
45
Communication wire
Power wire
Distribution box
(n-1)# IDU
Q L
P
P
N
Ln
Communication wire
Power wire
Distribution box
(n-1)# IDU
P Q
E
L
N
Ln
Main control board
Q
E
P
The shield layer must
be grounded
Connect to the ODU PQE
n# IDU
Q L
N
Resister
Figure 5.46
n# IDU
P Q
E
L
N
Resister
Figure 5.47
Figure 5.48