Page 1
FULL DC INVERTER SYSTEMS TECHNICAL SERVICE MANUAL INDOOR UNITS WITH DC FAN MOTOR C O M M E R C I A L A I R C O N D I T I O N E R S S D V 4...
Page 2
Original instructions The pictures of units and accessories are illustrative only. Technical specifications of the products are subject of change based on further development of the units by the producer and may be changed without prior notice...
Content Compact four-way cassette units ........4 Four-way cassette units ..........22 Wall mounted units ............44 Ceiling & floor standing units ........66 Duct units ............... 92 High static pressure duct units ........120 Fresh air processing duct units ......... 150 Due to the DC fan motor, these indoor unit can meet the latest CE certification requirements.
Page 4
Compact four-way cassette indoor units with DC fan motor...
Compact four-way cassette indoor units with DC fan motor Compact four-way cassette indoor units with DC fan motor Features ................5 Specifications ..............7 Dimensions ................9 Service Spaces ..............10 Piping Diagrams (EXV beside) ........11 Wiring Diagrams ..............12 Capacity Tables ..............
Compact four-way cassette indoor units with DC fan motor Features 1.1 Low operation noise, quiet design for user comfort Streamline plate ensures quietness Creates natural and comfortable environment 1.2 Efficient cooling Equal, fast and wide—range cooling 1.3 The adoption of the most advanced 3- Dimensional Screw fan Reduces the air resistance passing through and operating sound.
Page 7
Compact four-way cassette indoor units with DC fan motor 1.8 Adopting DC fan motor. 1.8.1 Efficiency can be up to 90%. Contrast with the AC fan motor, the power consumption of DC fan motor can reduce up to 30%. 1.8.2 The motor adopts fully enclosed structure design.
Compact four-way cassette indoor units with DC fan motor Specifications Model SDV4-22CAF SDV4-28CAF Power supply V-ph-Hz 220-240V~1Ph~50/60Hz Capacity Input Cooling Rated current 0.26 0.26 Capacity Input Heating Rated current 0.26 0.26 Model WZDK37-38G WZDK37-38G Type DC Motor DC Motor Indoor fan...
Page 9
Compact four-way cassette indoor units with DC fan motor Model SDV4-36CAF SDV4-45CAF Power supply V-ph-Hz 220-240V~1Ph~50/60Hz 220-240V~1Ph~50/60Hz Capacity Cooling Input Rated current 0.28 0.28 Capacity Heating Input Rated current 0.28 0.28 Model WZDK37-38G WZDK37-38G Type DC Motor DC Motor Indoor fan...
Compact four-way cassette indoor units with DC fan motor Service Spaces There is enough room for installation and maintenance. The ceiling is horizontal, and its structure can endure the weight of the indoor unit. The outlet and the inlet are not impeded, and the influence of external air is the least. The air flow can reach throughout the room.
Compact four-way cassette indoor units with DC fan motor Piping Diagrams (EXV beside) motor flare nut gas side heat exchanger flare nut liquid side T1: Room temperature; T2: Temperature of middle evaporator; T2B: Temperature of evaporator outlet.
Compact four-way cassette indoor units with DC fan motor Capacity Tables 7.1 Cooling TC: total capacity SC: sensible capacity WB: wet-bulb temperature DB: dry-bulb temperature Indoor temperature (°C WB/DB) Indoor Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 Unit size temperature (kW) (°C DB)
Page 16
Compact four-way cassette indoor units with DC fan motor Indoor temperature (°C WB/DB) Indoor Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 Unit size temperature (kW) (°C DB)
Page 17
Compact four-way cassette indoor units with DC fan motor 7.2 Heating TC: total capacity WB: wet-bulb temperature DB: dry-bulb temperature Indoor temperature (°C DB) Outdoor temperature Indoor Unit (°C) size (kW) -19,8 1.34 1.34 1.34 1.34 1.34 1.34 -18,8 1.44 1.44 1.44 1.44...
Page 18
Compact four-way cassette indoor units with DC fan motor Indoor temperature (°C DB) Outdoor temperature Indoor Unit (°C) size (kW) -19,8 2.24 2.24 2.24 2.24 2.24 2.24 -18,8 2.40 2.40 2.40 2.40 2.40 2.40 -16,7 2.52 2.52 2.52 2.52 2.52 2.52 -14,7 2.60...
Compact four-way cassette indoor units with DC fan motor Electrical Characteristics Indoor Unit Power Supply Model Voltage Min. Max. SDV4-22CAF 50/60 220-240 0.28 0.037 0.22 SDV4-28CAF 50/60 220-240 0.28 0.037 0.22 SDV4-36CAF 50/60 220-240 0.33 0.037 0.26 SDV4-45CAF 50/60 220-240 0.33...
Semi-anechoic chamber conversion value, measured at a point which is 1.4m under the unit. 9.2 Test values Sound level dB(A) Model SDV4-22CAF SDV4-28CAF SDV4-36CAF SDV4-45CAF 9.3 Octave Band Level SDV4-22CAF, SDV4-28CAF SDV4-36CAF, SDV4-45CAF Audibility limits of Audibility limits of continuous white continuous white sound sound Octave band center frequency ( Hz )...
Four way cassette indoor units with DC fan motor Four-way cassette indoor units with DC fan motor Features ..............23 Specifications ............25 Dimensions ............26 Service spaces ............28 Piping diagrams ............ 29 Wiring diagrams ............ 30 Capacity tables ............31 Electrical characteristics ........
Four-way cassette indoor units with DC fan motor Features External appearance Regardless of difference in capacity, all indoor units feature the same panel size and design, in consideration or harmonized interior decoration. Four way uniform airflow Four air discharge ports provide strong air flow circulation to cool or heat every corner of a room and evenly distribute temperature.
Page 25
Four way cassette indoor units with DC fan motor Duct connection is possible. Fresh air makes life healthier and more comfortable. Provided with high lift 700mm drain water pump.
Four-way cassette indoor units with DC fan motor Specifications Model SDV4-56CAF SDV4-71CAF SDV4-80CAF Power supply 220-240V~50/60Hz Capacity Cooling Power input Capacity Heating Power input Model WZDK80-38G Type DC motor Brand Shibaura Indoor fan motor Insulation class Safe class IP20 Input...
Page 27
Four way cassette indoor units with DC fan motor Model SDV4-90CAF SDV4-100CAF SDV4-112CAF SDV4-140CAF Power supply 220-240V~50/60Hz Capacity 10.0 11.2 14.0 Cooling Power input Capacity 10.0 11.1 12.5 15.0 Heating Power input Model WZDK90-38G Type DC motor Brand Shibaura Indoor fan motor...
Four way cassette indoor units with DC fan motor Service spaces There is enough room for installation and maintenance. The ceiling is horizontal, and its structure can endure the weight of the indoor unit. The outlet and the inlet are not impeded, and the influence of external air is the least. The air flow can reach throughout the room.
Four-way cassette indoor units with DC fan motor Piping diagrams motor flare nut gas side heat exchanger flare nut liquid side T1: Room temperature; T2: Temperature of middle evaporator; T2B: Temperature of evaporator outlet. Refrigerant pipe connection port diameters Unit: mm Model Gas pipe Liquid pipe...
Four-way cassette indoor units with DC fan motor Capacity tables 7.1 Cooling capacity tables TC: Total Cooling Capacity SC: Sensible Cooling Capacity Indoor air temp. (°C WB/DB) Unit Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 size air temp. (kW) (°C DB)
Page 33
Four way cassette indoor units with DC fan motor Indoor air temp. (°C WB/DB) Unit Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 size air temp. (kW) (°C DB) 10.4 10.2 10.2 10.0 10.6 11.7 10.6 11.5 10.6 11.4 10.6 11.3 10.6 11.0...
Page 34
Four-way cassette indoor units with DC fan motor Indoor air temp. (°C WB/DB) Unit Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 size air temp. (kW) (°C DB) 10.0 10.6 11.9 13.0 10.0 10.6 11.9 12.8 10.0 10.6 11.9 12.7 10.0 10.6 11.9...
Page 35
Four way cassette indoor units with DC fan motor Indoor air temp. (°C WB/DB) Unit Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 size air temp. (kW) (°C DB) 11.3 13.2 14.0 14.8 16.7 18.2 11.3 13.2 14.0 14.8 16.7 17.9 11.3 13.2...
Four-way cassette indoor units with DC fan motor 7.3 Heating capacity tables TC: Total Heating Capacity Indoor air temp. (°C DB) Outdoor Unit size air temp. (°C) (kW) -20.0 -19.8 3.53 3.53 3.53 3.53 3.53 3.53 -19.0 -18.8 3.78 3.78 3.78 3.78 3.78...
Page 37
Four way cassette indoor units with DC fan motor Indoor air temp. (°C DB) Outdoor Unit size air temp. (°C) (kW) -20.0 -19.8 5.04 5.04 5.04 5.04 5.04 5.04 -19.0 -18.8 5.40 5.40 5.40 5.40 5.40 5.40 -17.0 -16.7 5.67 5.67 5.67 5.67...
Page 38
Four-way cassette indoor units with DC fan motor Indoor air temp. (°C DB) Outdoor Unit size air temp. (°C) (kW) -20.0 -19.8 6.22 6.22 6.22 6.22 6.22 6.22 -19.0 -18.8 6.66 6.66 6.66 6.66 6.66 6.66 -17.0 -16.7 6.99 6.99 6.99 6.99 6.99...
Page 39
Four way cassette indoor units with DC fan motor Indoor air temp. (°C DB) Outdoor Unit size air temp. (°C) (kW) -20.0 -19.8 8.40 8.40 8.40 8.40 8.40 8.40 -19.0 -18.8 9.00 9.00 9.00 9.00 9.00 9.00 -17.0 -16.7 9.45 9.45 9.45 9.45...
Four-way cassette indoor units with DC fan motor Electrical characteristics Indoor unit Power supply Model Voltage Min. Max. SDV4-56CAF 50/60 220-240 0.53 0.035 0.42 SDV4-71CAF 50/60 220-240 0.67 0.044 0.53 SDV4-80CAF 50/60 220-240 0.67 0.044 0.53 SDV4-90CAF 50/60 220-240 1.25 0.088...
1. Sound values are measured in a seSDV4-anechoic room, at a position 1.4m downward from the unit center 2. During actual operation, these values are normally somewhat higher as a result of ambient conditions. Sound pressure level dB(A) Model SDV4-56CAF SDV4-71CAF SDV4-80CAF SDV4-90CAF...
Page 42
Four-way cassette indoor units with DC fan motor Octave band level SDV4-28CAF ~ SDV4-36CAF SDV4-45CAF ~ SDV4-56CAF Audibility limits of Audibility limits of continuous white continuous white sound sound Octave band center frequency ( Hz ) Octave band center frequency ( Hz )...
Four way cassette indoor units with DC fan motor Accessories Attached accessories Name Shape Quantity Washer Installation paper board Bolt M6 Connection pipe Soundproof / insulation sheath Sponge (250×250×10) Sponge (60×100×5) Outlet pipe sheath Outlet pipe clasp Tightening band Flexible hose tube Signal line Remote controller Frame...
Page 44
Wall mounted indoor units with DC fan motor...
Wall mounted indoor units with DC fan motor Wall mounted indoor units with DC fan motor Features ................45 Specifications ..............47 Dimensions ................ 49 Piping Diagrams ..............51 Wiring Diagrams ..............52 Capacity Tables ..............54 Electrical Characteristics ..........62 Sound Levels ..............
Wall mounted indoor units with DC fan motor 1. Features Design of the units. 1.2 Convenient for installation 1.2.1 Multi-refrigerant outlet pipe method: left\right\rear, more flexible for installation. Left Rear Right 1.2.2 Longer connection pipe, Gas pipe: 468mm /Liquid pipe: 550mm, more flexible for the installation. 1.2.3 Adopts new fixing plate, easy for installation and stable.
Page 47
Wall mounted indoor units with DC fan motor 1.4.2 Smoother airflow with less turbulence. Owing to the multiple-blade fan and the air guide design, the airflow is getting smoother and more comfortable. 1.4.3 Louver’s air swing angle can be up to 90º. 1.4.4 Advanced 3-D spiral fan design reduces air resistance and operating sound The motor bearing with unique design makes less operation vibration.
Wall mounted indoor units with DC fan motor 2. Specifications Model SDV4-22HAF SDV4-28HAF SDV4-36HAF SDV4-45HAF Power supply V-Ph-Hz 220-240V~, 1Ph, 50Hz Capacity Cooling Input Rated current 0.35 0.28 0.28 0.31 Capacity Heating Input 0.35 Rated current 0.28 0.28 0.31 WZDK20-38G...
Page 49
Wall mounted indoor units with DC fan motor SDV4-56HAF SDV4-71HAF SDV4-80HAF SDV4-90HAF Model Power supply V-Ph-Hz 220-240V~, 1Ph, 50/60Hz Capacity Input Cooling Rated current 0.41 0.49 0.68 0.68 Capacity 10.0 Heating Input Rated current 0.41 0.49 0.68 0.68 Model WZDK20-38G...
Wall mounted indoor units with DC fan motor 4. Piping Diagrams SDV4-22HAF, SDV4-28HAF, SDV4-36HAF, SDV4-45HAF, SDV4-56HAF motor flare nut gas side heat exchanger flare nut liquid side...
Wall mounted indoor units with DC fan motor 5. Wiring Diagrams SDV4-22HAF, SDV4-28HAF, SDV4-36HAF, SDV4-45HAF, SDV4-56HAF SDV4-71HAF, SDV4-80HAF, SDV4-90HAF...
Page 54
Wall mounted indoor units with DC fan motor Function setting indication...
Wall mounted indoor units with DC fan motor 6. Capacity Tables 6.1 Cooling TC: total capacity SC: sensible capacity WB: wet-bulb temperature DB: dry-bulb temperature Indoor temperature (°C, WB/DB) Indoor Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 unit temperature size (°C, WB) (kW)
Page 56
Wall mounted indoor units with DC fan motor Indoor temperature (°C, WB/DB) Indoor Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 unit temperature size (°C, WB) (kW) 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0...
Page 57
Wall mounted indoor units with DC fan motor Indoor temperature (°C, WB/DB) Indoo Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 r unit temperature size (°C, WB) (kW) 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0...
Page 58
Wall mounted indoor units with DC fan motor Indoor temperature (°C, WB/DB) Indoor Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 unit temperature size (°C, WB) (kW) 10.0 10.4 12.0 10.2 14.0 10.2 16.0 10.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0...
Page 59
Wall mounted indoor units with DC fan motor 6.2 Heating TC: total capacity WB: wet-bulb temperature DB: dry-bulb temperature Indoor temperature (°C, DB) Indoor Outdoor unit size temperature (°C) (kW) -19.8 1.34 1.34 1.34 1.34 1.34 1.34 -18.8 1.44 1.44 1.44 1.44 1.44...
Page 60
Wall mounted indoor units with DC fan motor Indoor temperature (°C, DB) Indoor Outdoor unit size temperature (°C) (kW) -19.8 2.24 2.24 2.24 2.24 2.24 2.24 -18.8 2.40 2.40 2.40 2.40 2.40 2.40 -16.7 2.52 2.52 2.52 2.52 2.52 2.52 -13.7 2.60 2.60...
Page 61
Wall mounted indoor units with DC fan motor Indoor temperature (°C, DB) Indoor Outdoor unit size temperature (°C) (kW) -19.8 3.53 3.53 3.53 3.53 3.53 3.53 -18.8 3.78 3.78 3.78 3.78 3.78 3.78 -16.7 3.97 3.97 3.97 3.97 3.97 3.97 -13.7 4.10 4.10...
Page 62
Wall mounted indoor units with DC fan motor Indoor temperature (°C, DB) Indoor Outdoor unit size temperature (°C) (kW) -19.8 5.04 5.04 5.04 5.04 5.04 5.04 -18.8 5.40 5.40 5.40 5.40 5.40 5.40 -16.7 5.67 5.67 5.67 5.67 5.67 5.67 -13.7 5.85 5.85...
Wall mounted indoor units with DC fan motor 7. Electrical Characteristics Indoor Unit Power Supply Model Voltage Min. Max. SDV4-22HAF 220~240 0.24 0.02 0.19 SDV4-28HAF 220~240 0.24 0.02 0.19 SDV4-36HAF 220~240 0.28 0.02 0.22 SDV4-45HAF 220~240 0.31 0.02 0.25 SDV4-56HAF 220~240 0.36...
SDV4-45HAF SDV4-56HAF SDV4-71HAF SDV4-80HAF SDV4-90HAF SDV4-15HAF SDV4-22HAF SDV4-28HAF SDV4-36HAF SDV4-45HAF, SDV4-56HAF, SDV4-71HAF, SDV4-80HAF, SDV4-90HAF Audibility limits of Audibility limits of continuous white continuous white sound sound Octave band center frequency ( Hz ) Octave band center frequency ( Hz )...
Wall mounted indoor units with DC fan motor 9. Accessories 9.1 Standard accessories Name Quantity Shape Usage Remote controller manual Screw ST3.9x25 for Secure the installation board installation board Plastic expanded tube Wrapping tape Drain pipe Wall conduit cover Remote controller (including operation manual) Frame Hold the remote controller...
Page 66
Ceiling & floor standing indoor units with DC fan motor...
Ceiling & floor standing indoor units with DC fan motor Ceiling & floor indoor units with DC fan motor Features ................67 Specifications ..............69 Dimensions ................ 71 Service Spaces ..............72 Piping Diagrams ..............73 Wiring Diagrams ..............74 Capacity Tables ..............
Ceiling & floor standing indoor units with DC fan motor 1. Features Panel with LED display 1.7 Adopting DC fan motor Efficiency can be up to 90%. Contrast with the AC fan motor, the power consumption of DC fan motor can reduce up to 30%.
Page 69
Ceiling & floor standing indoor units with DC fan motor 1.12 Wired control compatible RM05 remote wireless controller which can set the indoor unit address is standard, and wired controller is optional. 1.13 Auto restart When the indoor unit is powered off, it will auto restart when powered on again after 3 minutes and operate in the original state.
Ceiling & floor standing indoor units with DC fan motor 2. Specifications SDV4-36FAF SDV4-45FAF SDV4-56FAF SDV4-71FAF Model Power supply V- Ph-Hz 220-240V, 1Ph, 50/60Hz Capacity Cooling Input Rated current 0.32 0.72 0.72 0.72 Capacity Heating Input Rated current 0.32 0.72 0.72...
Page 71
Ceiling & floor standing indoor units with DC fan motor SDV4-80FAF SDV4-90FAF SDV4-112FAF SDV4-140FAF Model Power supply V- Ph-Hz 220-240V, 1Ph, 50/60Hz Capacity 11.2 Cooling Input 65*2 65*2 Rated current 1.14 1.14 0.6*2 0.6*2 Capacity 12.5 15.5 Heating Input 65*2...
Ceiling & floor standing indoor units with DC fan motor 4. Service Spaces SDV4-36FAF, SDV4-45FAF, SDV4-56FAF, SDV4-71FAF, SDV4-80FAF, SDV4-90FAF, SDV4-112FAF, SDV4-140FAF >600mm Obstacle Piping connection Keep more than 600mm clearance between the unit and left/right side wall. Air Outlet Obstacle 600mm As well 600mm and up between the front panel and wall.
Ceiling & floor standing indoor units with DC fan motor 5. Piping Diagrams SDV4-36FAF, SDV4-45FAF, SDV4-56FAF, SDV4-71FAF, SDV4-80FAF, SDV4-90FAF, SDV4-112FAF, SDV4-140FAF motor flare nut gas side heat exchanger flare nut liquid side...
Ceiling & floor standing indoor units with DC fan motor 6. Wiring Diagrams SDV4-36FAF, SDV4-45FAF, SDV4-56FAF, SDV4-71FAF, SDV4-80FAF, SDV4-90FAF...
Page 76
Ceiling & floor standing indoor units with DC fan motor SDV4-140FAF...
Page 77
Ceiling & floor standing indoor units with DC fan motor Power settings ENC1 switch code Cooling power output 2800W 3600W 4500W 5600W 7100W 8000W 9000W 10000W 11200W 14000W 16000W Note: Base on different purposes to setting the switch cords on PC panel of indoor electrical control box. Once finish the setting, please cut off the main power, and then input power again, otherwise, setting function could not work.
Page 78
Ceiling & floor standing indoor units with DC fan motor SW5 definition SW6 definition SW7 definition J1,J2 definition 0/1 definition...
Ceiling & floor standing indoor units with DC fan motor 7. Capacity Tables 7.1 Cooling TC: total capacity SC: sensible capacity WB: wet-bulb temperature DB: dry-bulb temperature Indoor temperature (°C WB/DB) Indoor Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 Unit size temperature (kW)
Page 80
Ceiling & floor standing indoor units with DC fan motor Indoor temperature (°C WB/DB) Indoor Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 Unit size temperature (kW) (°C DB) 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0...
Page 81
Ceiling & floor standing indoor units with DC fan motor Indoor temperature (°C WB/DB) Indoor Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 Unit size temperature (kW) (°C DB) 10.0 10.6 11.7 12.0 10.6 11.5 14.0 10.6 11.4 16.0 10.6 11.3 18.0 10.6...
Page 82
Ceiling & floor standing indoor units with DC fan motor 10.0 11.3 13.2 14.0 14.8 16.7 18.2 12.0 11.3 13.2 14.0 14.8 16.7 17.9 14.0 11.3 13.2 14.0 14.8 16.7 17.8 16.0 11.3 13.2 14.0 14.8 16.7 17.5 18.0 11.3 13.2 14.0 14.8...
Page 83
Ceiling & floor standing indoor units with DC fan motor 7.2 Heating TC: total capacity WB: wet-bulb temperature DB: dry-bulb temperature Indoor temperature (°C DB) Outdoor temperature Indoor Unit size (°C) (kW) -19.8 2.24 2.24 2.24 2.24 2.24 2.24 -18.8 2.40 2.40 2.40...
Page 84
Ceiling & floor standing indoor units with DC fan motor Indoor temperature (°C DB) Outdoor temperature Indoor Unit size (°C) (kW) -19.8 3.53 3.53 3.53 3.53 3.53 3.53 -18.8 3.78 3.78 3.78 3.78 3.78 3.78 -16.7 3.97 3.97 3.97 3.97 3.97 3.97 -14.7...
Page 85
Ceiling & floor standing indoor units with DC fan motor Indoor temperature (°C DB) Outdoor temperature Indoor Unit size (°C) (kW) -19.8 5.60 5.04 5.60 5.60 5.60 5.60 -18.8 6.00 5.40 6.00 6.00 6.00 6.00 -16.7 6.30 6.30 6.30 6.30 6.30 6.30 -14.7...
Page 86
Ceiling & floor standing indoor units with DC fan motor Indoor temperature (°C DB) Outdoor temperature Indoor Unit size (°C) (kW) -19.8 8.68 8.68 8.68 8.68 8.68 8.68 -18.8 9.30 9.30 9.30 9.30 9.30 9.30 -16.7 9.77 9.77 9.77 9.77 9.77 9.77 -14.7...
Ceiling & floor standing indoor units with DC fan motor 8. Electrical Characteristics Indoor Unit Power Supply Model Voltage Min. Max. SDV4-36FAF 50/60 220-240 0.32 0.020 0.15 SDV4-45FAF 50/60 220-240 0.89 0.080 0.72 SDV4-56FAF 50/60 220-240 0.89 0.080 0.72 SDV4-71FAF...
2. Anechoic chamber conversion value, measured at a point 1m in front of the unit at a height of 1.5m. 9.2 Test data (Sound Pressure Levels) Sound level under three speeds of fan (dB(A)) Model SDV4-36FAF SDV4-45FAF SDV4-56FAF SDV4-71FAF SDV4-80FAF...
Ceiling & floor standing indoor units with DC fan motor 9.3 Octave Band Level SDV4-36FAF SDV4-45FAF SDV4-56FAF SDV4-71FAF Audibility limits of Audibility limits of continuous white continuous white sound sound Octave band center frequency ( Hz ) Octave band center frequency ( Hz )...
Ceiling & floor standing indoor units with DC fan motor 10. Accessories Name Quantity Shape Usage Installation manual Hook Hanging arm Drainage pipe Drainage Pipe insulation material Heat insulation for drainage pipe Bolt assembly Use for pipe connection of engineering Copper installation Remote controller...
Page 91
Ceiling & floor standing indoor units with DC fan motor...
Page 92
Concealed duct indoor units with DC fan motor...
Concealed duct indoor units with DC fan motor Concealed duct units with DC fan motor 1. Features ................. 93 2. Specifications ..............95 3. Dimensions ..............100 4. Service Spaces ............102 5. Piping Diagrams ............103 6. Wiring Diagrams ............104 7.
Compact design Only 210 mm (SDV4-22DAF to SDV4-71DAF) or 270mm (SDV4-80DAF to SDV4-112DAF models) or 300mm (SDV4-140DAF) in height, these models can be installed in rooms with as little as 240mm~300 mm height between the drop ceiling and ceiling slab.
Page 95
1.4.2 The display board is connected with the E-box in factory, which makes troubleshooting easier by LED display. SDV4-22DAF to SDV4-71DAF SDV4-80DAF to SDV4-140DAF 1.4.3 The electrical control box is possible to remove 1m far away from the main unit, which is suitable for the small space hard to maintain.
Concealed duct indoor units with DC fan motor 2. Specifications Model SDV4-22DAF SDV4-28DAF Power supply V-Hz-Ph 220-240V~50/60Hz Capacity Cooling Input 0.31 0.31 Rated current Capacity Heating Input 0.31 0.31 Rated current WZDK100-38GS WZDK100-38GS Model Type DC motor DC motor Indoor fan...
Page 97
Concealed duct indoor units with DC fan motor Model SDV4-36DAF SDV4-45DAF Power supply V-Hz-Ph 220-240V~50/60Hz Capacity Cooling Input Rated current 0.33 0.36 Capacity Heating Input Rated current 0.33 0.36 Model WZDK100-38GS WZDK100-38GS-2 Type DC motor DC motor Indoor fan Brand...
Page 98
Concealed duct indoor units with DC fan motor Model SDV4-56DAF SDV4-71DAF Power supply V-Hz-Ph 220-240V~50/60Hz Capacity Cooling Input Rated current 0.36 0.47 Capacity Heating Input Rated current 0.36 0.47 Model WZDK100-38GS-2 WZDK100-38GS-1 Type DC motor DC motor Indoor fan motor...
Page 99
Concealed duct indoor units with DC fan motor SDV4-90DAF Model SDV4-80DAF Power supply V- Ph-Hz 220-240V~50/60Hz Capacity Cooling Input Rated current Capacity Heating Input Rated current Model WZDK150-38GS WZDK150-38GS Type DC motor DC motor Indoor fan Brand Pansonic/Nidec/Welling Pansonic/Nidec/Welling motor...
Page 100
Concealed duct indoor units with DC fan motor Model SDV4-112DAF SDV4-140DAF Power supply V- Ph-Hz 220-240V~50/60Hz Capacity 11.2 Cooling Input Rated current 1.55 Capacity 12.5 15.5 Heating Input Rated current 1.55 Model WZDK150-38GS WZDK240-38GS Type DC motor DC motor Indoor fan...
Concealed duct indoor units with DC fan motor 3. Dimensions For models: SDV4-15DAF, SDV4-22DAF, SDV4-28DAF, SDV4-36DAF SDV4-45DAF, SDV4-56DAF, SDV4-71DAF, SDV4-80DAF, SDV4-90DAF, SDV4-112DAF, SDV4-140DAF Outline dimension and air outlet opening size: (Unit: mm) Air return opening size: Air filter Position size of declensional ventilation opening:...
Page 102
Concealed duct indoor units with DC fan motor Outline dimension Air outlet opening size Model (SDV4-**DAF) 22~36 45~56 1000 1140 1220 80~112 1140 1230 1200 1290 Air return opening size Size of mounted lug Model (SDV4-**DAF) 22~36 45~56 1040 1180...
Concealed duct indoor units with DC fan motor 4. Service Spaces Ensure the needed spaces for installation and maintenance. The ceiling is horizontal and its structure can endure the weight of the indoor unit. The outlet and the inlet are not impeded, and the influence of external air is the least. ...
Concealed duct indoor units with DC fan motor 6. Wiring Diagrams For models: SDV4-15DAF, SDV4-22DAF, SDV4-28DAF, SDV4-36DAF , SDV4-45DAF, SDV4-56DAF, SDV4-71DAF, SDV4-80DAF, SDV4-90DAF, SDV4-112DAF, SDV4-140DAF...
Concealed duct indoor units with DC fan motor 7. Fan Performance How to read the diagram For static pressure dial code, please see the following Table: Medium High ENC2 static pressure static pressure static pressure Model 22-71 0 - 15Pa 10 - 25Pa 15 - 30Pa 80-90...
Page 107
Concealed duct indoor units with DC fan motor 1000 1100 1000 1100 m3/h m3/h Model:45 Model:56 400 600 1000 1200 1400 1600 1800 2000 1000 1200 1400 m3/h m3/h Model:71 Model:80~90 1000 1250 1500 1750 2000 2250 2500 1000 1500 2000 2500 3000...
Concealed duct indoor units with DC fan motor 8. Capacity Tables 8.1 Cooling TC: Total capacity SC: Sensible capacity WB: Wet-bulb temperature DB: Dry-bulb temperature Indoor temperature (°C WB/DB) Indoor Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 Unit size temperature (kW) (°C DB)
Page 109
Concealed duct indoor units with DC fan motor Indoor temperature (°C WB/DB) Indoor Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 Unit size temperature (kW) (°C DB) 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0...
Page 110
Concealed duct indoor units with DC fan motor Indoor temperature (°C WB/DB) Indoor Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 Unit size temperature (kW) (°C DB) 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0...
Page 111
Concealed duct indoor units with DC fan motor Indoor temperature (°C WB/DB) Indoor Outdoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 Unit size temperature (kW) (°C DB) 10.0 10.5 11.2 11.9 13.3 15.5 12.0 10.5 11.2 11.9 13.3 14.4 14.0 10.5 11.2 11.9...
Page 112
Concealed duct indoor units with DC fan motor 8.2 Heating TC: Total capacity WB: Wet-bulb temperature DB: Dry-bulb temperature Indoor temperature (°C DB) Outdoor temperature Indoor Unit size (°C ) (kW) -20.00 -19.80 1.46 1.46 1.46 1.46 1.46 1.46 -19.00 -18.80 1.56 1.56...
Page 113
Concealed duct indoor units with DC fan motor Indoor temperature (°C DB) Outdoor temperature Indoor Unit size (°C ) (kW) -20.00 -19.80 2.80 2.80 2.80 2.80 2.80 2.80 -19.00 -18.80 3.00 3.00 3.00 3.00 3.00 3.00 -17.00 -16.70 3.15 3.15 3.15 3.15 3.15...
Page 114
Concealed duct indoor units with DC fan motor Indoor temperature (°C DB) Outdoor temperature Indoor Unit size (°C ) (kW) -19.8 5.04 5.04 5.04 5.04 5.04 5.04 -18.8 5.40 5.40 5.40 5.40 5.40 5.40 -16.7 5.67 5.67 5.67 5.67 5.67 5.67 -14.7 5.85...
Page 115
Concealed duct indoor units with DC fan motor Indoor temperature (°C DB) Outdoor temperature Indoor Unit size (°C ) (kW) -19.8 8.68 8.68 8.68 8.68 8.68 8.68 -18.8 9.30 9.30 9.30 9.30 9.30 9.30 -16.7 9.77 9.77 9.77 9.77 9.77 9.77 -14.7 10.08...
Concealed duct indoor units with DC fan motor 9. Electrical Characteristics Indoor Unit Power Supply Model Voltage Min. Max. SDV4-22DAF 50/60 220-240 0.375 0.017 SDV4-28DAF 50/60 220-240 0.375 0.017 SDV4-36DAF 50/60 220-240 0.375 0.02 SDV4-45DAF 50/60 220-240 0.028 SDV4-56DAF 50/60 220-240 0.034...
Model SDV4-22DAF SDV4-28DAF SDV4-36DAF SDV4-45DAF SDV4-56DAF SDV4-71DAF SDV4-80DAF SDV4-90DAF SDV4-112DAF SDV4-140DAF SDV4-22DAF, SDV4-28DAF SDV4-36DAF Audibility limits of Audibility limits of continuous white continuous white sound sound Octave band center frequency ( Hz ) Octave band center frequency ( Hz )...
Page 118
Concealed duct indoor units with DC fan motor SDV4-45DAF, SDV4-56DAF SDV4-71DAF Audibility limits of Audibility limits of continuous white continuous white sound sound Octave band center frequency ( Hz ) Octave band center frequency ( Hz ) SDV4-80DAF, SDV4-90DAF SDV4-112DAF...
Concealed duct indoor units with DC fan motor 11. Accessories 11.1 Standard accessories For models: SDV4-15DAF, SDV4-22DAF, SDV4-28DAF, SDV4-36DAF, SDV4-45DAF, SDV4-56DAF, SDV4-71DAF, SDV4-80DAF, SDV4-90DAF, SDV4-112DAF, SDV4-140DAF Name Quantity Shape Usage Installation manual This manual Wire controller Wire control the air-conditioner...
Page 120
High static pressure duct indoor units with DC fan motor...
High static pressure duct indoor units with DC fan motor High static pressure duct units with DC fan motor 1. Features ................ 121 2. Specifications .............. 123 3. Dimensions ..............125 4. Service Spaces ............132 5. Piping Diagrams ............133 6.
High static pressure duct indoor units with DC fan motor 1. Features Flexibility in duct design 1.1.1 External static pressure of Indoor Unit can be up to 280 Pa, which allows for extensive duct work and therefore more flexibility. Challenges such as high ceilings can be overcome and cool air delivered to every corner of a room.
High static pressure duct indoor units with DC fan motor DC fan motor Adoption of a DC fan motor can raise efficiency up to 90%. When compared with an AC fan motor, power consumption can be reduced by up to 30% with a DC fan motor. Power Inpu t:W DC and AC motors power contrast DC moto r...
High static pressure duct indoor units with DC fan motor 2. Specifications Model SDV4-71DHAF SDV4-80DHAF SDV4-90DHAF Power supply V-Ph-Hz 220-240V~50/60Hz Capacity Cooling Input Rated current Capacity 10.0 Heating Input Rated current Model WZDK240-38G WZDK240-38G WZDK750-38G-W Indoor Type DC Motor Brand...
Page 125
High static pressure duct indoor units with DC fan motor Model SDV4-112DHAF SDV4-140DHAF SDV4-160DHAF Power supply V-Ph-Hz 220-240V~50/60Hz Capacity 11.2 Cooling Input Rated current Capacity 12.5 Heating Input Rated current Model WZDK750-38G-W WZDK750-38GS-W WZDK750-38GS-W Indoor Type DC MOTOR Brand Pansonic/Nidec/Welling...
Page 126
High static pressure duct indoor units with DC fan motor Model SDV4-200DHAF SDV4-250DHAF SDV4-280DHAF Power supply V-Ph-Hz 220-240V~50/60Hz Capacity 20.0 25.0 28.0 Cooling Input Rated current Capacity 22.5 26.0 31.5 Heating Input Rated current Model WZDK750-38GS-W WZDK750-38GS-W WZDK750-38GS-W Indoor Type...
High static pressure duct indoor units with DC fan motor 3. Dimensions SDV4-71DHAF SDV4-80DHAF SDV4-90DHAF SDV4-112DHAF Front, top and rear views: Unit:in (mm) 37-11/32(952m m ) 3-3/8 34-1/16(856m m ) (86m m ) 8-7/16(214m m ) P LA S TIC C O V E R...
Page 128
High static pressure duct indoor units with DC fan motor Side view: Left side C O N N E C TIN G P O INT O F D R A IN P IP E REFRIGERANT-PIPE FLANGE CONNECTION R E FR IG E R A NT -P IP E FLA N E D 1-11/16 C O N N E C TIO N Φ...
Page 129
High static pressure duct indoor units with DC fan motor SDV4-140DHAF SDV4-160DHAF Front, top and rear views: Unit:in(mm) A IR O U TLE T 42-1/4(1073m m ) 2-17/32 (64m m )
Page 130
High static pressure duct indoor units with DC fan motor Side view: Left side C O N N E C TIN G P O INT O F D R A IN P IP E REFRIGERANT-PIPE R E FR IG E R A NT -P IP E FLA N E D 1-11/16 C O N N E C TIO N Φ...
Page 131
High static pressure duct indoor units with DC fan motor SDV4-200DHAF SDV4-250DHAF SDV4-280DHAF Front, top and rear views: Unit:in (mm) 44-9/64(1121) 2-61/64(75) Entrances and exits for communication lines of indoor and outdoor Air outlet 4-12*25 oblong 56-13/16(1443) suspention bolt holes...
Page 132
High static pressure duct indoor units with DC fan motor Key installation points for the 200, 250, 280 models: There are two sets of EXV boxes for models 200, 250 and 280, as well two sets of pipes (gas/liquid), it’s necessary to connect the two gas pipes together with the attached branch header SDV-BY101N1 as well the liquid pipes.
High static pressure duct indoor units with DC fan motor 4. Service Spaces Ensure sufficient space for installation and maintenance. The ceiling must be horizontal, and is structurally capable of carrying the weight of the indoor unit. The outlet and the inlet are not impeded, and little influence of external air is the least.
High static pressure duct indoor units with DC fan motor 5. Piping Diagrams SDV4-71DHAF, SDV4-80DHAF, SDV4-90DHAF, SDV4-112DHAF, SDV4-140DHAF, SDV4-160DHAF motor flare nut gas side heat exchanger flare nut liquid side SDV4-200DHAF, SDV4-250DHAF, SDV4-280DHAF motor motor flare nut flare nut gas side...
High static pressure duct indoor units with DC fan motor 6. Wiring Diagrams SDV4-71DHAF, SDV4-80DHAF, SDV4-90DHAF, SDV4-112DHAF, SDV4-140DHAF, SDV4-160DHAF...
Page 136
High static pressure duct indoor units with DC fan motor SDV4-200DHAF, SDV4-250DHAF, SDV4-280DHAF...
High static pressure duct indoor units with DC fan motor 7. Fan Performance Heating and cooling capacity are tested under the standard allowable static pressure; the 71 test static pressure is 25Pa, 80/90/112 test static pressure is 37Pa, 140/160 test static pressure is 50Pa, the 200/250/280 test pressure is 62Pa.
Page 138
High static pressure duct indoor units with DC fan motor If the external static pressure is too high, caused by extensive ducting for example, the air flow volume at each outlet may be reduced to insufficient levels. So there’s a limit air flow volume for each speed, which is the min. airflow of this duct unit. At this flow volume, the fan achieve the max.
High static pressure duct indoor units with DC fan motor 8. Capacity Tables 8.1 Cooling TC: total capacity SC: sensible capacity WB: wet-bulb temperature DB: dry-bulb temperature Indoor temperature (°C WB/DB) Indoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 Outdoor temperature Unit size (°C DB) (kW)
Page 140
High static pressure duct indoor units with DC fan motor Indoor temperature (°C WB/DB) Indoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 Outdoor temperature Unit size (°C DB) (kW) 10.0 10.5 11.2 11.9 13.3 14.6 12.0 10.5 11.2 11.9 13.3 14.3 14.0 10.5...
Page 141
High static pressure duct indoor units with DC fan motor Indoor temperature (°C WB/DB) Indoor 14/20 16/23 18/26 19/27 20/28 22/30 24/32 Outdoor temperature Unit size (°C DB) (kW) 10.0 13.8 12.1 16.2 13.3 18.8 14.8 20.0 15.1 21.2 15.1 23.8 15.7 26.0...
Page 142
High static pressure duct indoor units with DC fan motor 8.2 Heating TC: total capacity WB: wet-bulb temperature DB: dry-bulb temperature Indoor temperature (°C DB) Outdoor temperature Indoor Unit size (°C) (kW) -19.8 3.98 3.98 3.98 3.98 3.98 3.98 -18.8 4.26 4.26 4.26...
Page 143
High static pressure duct indoor units with DC fan motor Indoor temperature (°C DB) Outdoor temperature Indoor Unit size (°C) (kW) -19.8 6.27 6.27 6.27 6.27 6.27 6.27 -18.8 6.72 6.72 6.72 6.72 6.72 6.72 -16.7 7.06 7.06 7.06 7.06 7.06 7.06 -14.7...
Page 144
High static pressure duct indoor units with DC fan motor Indoor temperature (°C DB) Outdoor temperature Indoor Unit size (°C) (kW) -19.8 11.20 11.20 11.20 11.20 11.20 11.20 -18.8 12.00 12.00 12.00 12.00 12.00 12.00 -16.7 12.60 12.60 12.60 12.60 12.60 12.60 -14.7...
High static pressure duct indoor units with DC fan motor 9. Electrical Characteristics Indoor Unit Power Supply Model Voltage Min. Max. SDV4-71DHAF 50/60 220-240 0.17 1.35 SDV4-80DHAF 50/60 220-240 0.17 1.35 SDV4-90DHAF 50/60 220-240 SDV4-112DHAF 50/60 220-240 0.37 2.88 SDV4-140DHAF...
High static pressure duct indoor units with DC fan motor 10. Sound Levels 10.1 Test conditions 10.2 Test value Sound test value dB(A) Model SDV4-71DHAF SDV4-80DHAF SDV4-90DHAF SDV4-112DHAF SDV4-140DHAF SDV4-160DHAF SDV4-200DHAF SDV4-250DHAF SDV4-280DHAF SDV4-71DHAF SDV4-80DHAF SDV4-90DHAF, SDV4-112DHAF...
Page 147
High static pressure duct indoor units with DC fan motor SDV4-140DHAF SDV4-160DHAF SDV4-200DHAF, SDV4-250DHAF, SDV4-280DHAF...
High static pressure duct indoor units with DC fan motor 11. Accessories 11.1 Standard accessories Name Qty. Shape Usage Installation manual 7.1~16kW Pipe insulation material Heat insulation 20~28kW Form a sealed drain pipe Adhesive tape 20~28kW connection Water outlet joint 7.1~16kW For drainage pipe Wired controller (KJR-29B)
Page 149
High static pressure duct indoor units with DC fan motor...
Page 150
Fresh air processing duct indoor units with DC fan motor...
Fresh air processing duct indoor units with DC fan motor Fresh air processing duct units with DC fan motor 1. Features ................151 2. Specifications ..............152 3. Dimensions ..............153 4. Service Spaces ............... 156 5. Piping Diagrams ............. 157 6.
1.4 Wired control and group control available. 1.5 High capacity of cooling/heating and efficient. 1.6 Innovative air supply, which provides homogeneous conditioning of the room temperature. 1.7 Can be connected to all Sinclair SDV systems except 3-pipe installations and small outdoor units. Layout Example:...
Fresh air processing duct indoor units with DC fan motor 2. Specifications Model SDV4-125DFAF SDV4-140DFAF Power supply V-Ph-Hz 220-240V~50/60Hz 220-240V~50/60Hz Capacity 12.5 Cooling Input Rated current Capacity 10.5 Heating Input Rated current Model WZDK750-38GS-W WZDK750-38GS-W Type DC Motor DC Motor...
Page 154
Fresh air processing duct indoor units with DC fan motor Model SDV4-200DFAF SDV4-250DFAF SDV4-280DFAF Power supply V-Ph-Hz 220-240V~50/60Hz 220-240V~50/60Hz 220-240V~50/60Hz Capacity 20.0 25.0 28.0 Cooling Input Rated current Capacity 18.0 20.0 22.0 Heating Input Rated current Model WZDK750-38GS-W WZDK750-38GS-W WZDK750-38GS-W...
Fresh air processing duct indoor units with DC fan motor 3. Dimensions SDV4-125DFAF, SDV4-140DFAF Unit: mm Plastic cover Electrical control box Air intake 4-12*25 oblong suspention bolt holes 1148 Drain pipe connecting point 4-φ5 holes for air Air intake duct flange...
Page 156
Fresh air processing duct indoor units with DC fan motor SDV4-200DFAF, SDV4-250DFAF, SDV4-280DFAF...
Fresh air processing duct indoor units with DC fan motor 5. Piping Diagrams motor motor flare nut flare nut gas side flare nut liquid side heat exchanger flare nut liquid side...
Fresh air processing duct indoor units with DC fan motor 7. Capacity Tables 7.1 SDV4-125DFAF TC: total capacity WB: wet-bulb temperature DB: dry-bulb temperature Cooling °C WB Outdoor temperature 15.0 17.0 20.0 23.0 26.0 28.0 30.0 32.0 °C DB Capacity (TC) 20.0...
Page 162
Fresh air processing duct indoor units with DC fan motor 7.2 SDV4-140DFAF TC: total capacity WB: wet-bulb temperature DB: dry-bulb temperature Cooling °C WB Outdoor temperature 15.0 17.0 20.0 23.0 26.0 28.0 30.0 32.0 °C DB Capacity (TC) 20.0 22.0 25.0...
Page 163
Fresh air processing duct indoor units with DC fan motor SDV4-200DFAF TC: total capacity WB: wet-bulb temperature DB: dry-bulb temperature Cooling °C WB Outdoor temperature 15.0 17.0 20.0 23.0 26.0 28.0 30.0 32.0 °C DB Capacity (TC) 20.0 22.0 10.0 11.1...
Page 164
Fresh air processing duct indoor units with DC fan motor 7.4 SDV4-250DFAF TC: total capacity WB: wet-bulb temperature DB: dry-bulb temperature Cooling °C WB Outdoor temperature 15.0 17.0 20.0 23.0 26.0 28.0 30.0 32.0 °C DB Capacity (TC) 20.0 11.2 12.1...
Page 165
Fresh air processing duct indoor units with DC fan motor 7.5 SDV4-280DFAF TC: total capacity WB: wet-bulb temperature DB: dry-bulb temperature Cooling °C WB Outdoor temperature 15.0 17.0 20.0 23.0 26.0 28.0 30.0 32.0 °C DB Capacity 20.0 12.5 13.6 22.0...
Fresh air processing duct indoor units with DC fan motor 8. Electrical Characteristics Indoor Unit Power Supply Model Voltage Min. Max. SDV4-125DFAF 50/60 220-240V 198V 254V SDV4-140DFAF 50/60 220-240V 198V 254V SDV4-200DFAF 50/60 220-240V 198V 254V SDV4-250DFAF 50/60 220-240V 198V...
Fresh air processing duct indoor units with DC fan motor 9. Fan Performance Heating and cooling capacities are tested under the standard allowable static pressure; the 125/140 test static pressure is 50Pa, the 200/250/280 test pressure is 62Pa. If the external static pressure is too high, caused by extensive ducting for example, the air flow volume at each outlet may be reduced to insufficient levels.
1.4m Microphone Noise level under three speeds of fan (dB(A)) Model SDV4-125DFAF SDV4-140DFAF SDV4-200DFAF SDV4-250DFAF SDV4-280DFAF SDV4-125DFAF, SDV4-140DFAF SDV4-200DFAF Audibility limits of Audibility limits of continuous white continuous white sound sound Octave band center frequency ( Hz ) Octave band center frequency ( Hz )...
Fresh air processing duct indoor units with DC fan motor 11. Accessories Name Qty. Shape Usage Installation manual 12.5~14kW Pipe insulation material Heat insulation 20~28kW Adhesive tape for seal 20~28kW To connect drain pipe Water outlet joint 12.5~14kW For drainage Wired controller (KJR-29B) Control the air conditioner.
Page 170
The value GWP: 2088 GWP = Global Warming Potential In case of quality problem or other please contact your local supplier or authorized service center. Emergency number: 112 PRODUCER SINCLAIR CORPORATION Ltd. 1-4 Argyll St. LONDON W1F 7LD United Kingdom www.sinclair-world.com...