Download Print this page
lanry RC Series Manual

lanry RC Series Manual

Ultrasonic heat meter

Advertisement

Quick Links

RC Series Ultrasonic Heat Meter                                                        
General Description
RC Series ultrasonic heating (cooling, heating-cooling)
meters are used for energy measurement of heating or
chilled water in residential and small commercial heating
and air conditioning systems. They are available in
DN15...40 and have an electronic energy calculator with
separate register for heating and cooling energy. They
are fitted with an M-Bus interface for integration into M-
Bus networks.
Important Notice
Please read this manual carefully before undertaking
the installation!
RC Series ultrasonic heat meters must be installed by
qualified personnel in accordance with the instructions
given in this manual.
RC takes no responsibility for difficulties arising from
failure to observe these instructions.
Seals on the heat-meter must not be damaged.
Breaking or damaging meter seals is seen as
violation of the equipment.
It is not allowed to shorten and/or replace the
data or temperature sensor cables attached to the
product.
These instructions should be handed over to the user
upon completion of the installation. They should be kept
for future reference.
Installation
Before Installation
It is recommended to install a valve before and after
heat meter for maintenance and filter cleaning.
It is recommended to install a filter on inlet of heat
meter.
Figure 2. Recommended installation
Installation Precautions:
alve installation before and after heat meter and filter,
easy for heat meter maintenance and filter cleaning.
Please notice valve opening sequence: open
slowly valve before heat meter in inlet water side
firstly, then open valve after heat meter outlet water
side. Finally open valve in back water pipeline, to
protect heat meter due to sand, stone etc. impurity
which inside of pipeline of lower of heat meter flowing
back to meter body.
1
 

Advertisement

loading

Summary of Contents for lanry RC Series

  • Page 1 M-Bus interface for integration into M- Bus networks. Important Notice Please read this manual carefully before undertaking the installation! RC Series ultrasonic heat meters must be installed by Figure 2. Recommended installation qualified personnel in accordance with the instructions given in this manual. Installation Precautions: RC takes no responsibility for difficulties arising from failure to observe these instructions.
  • Page 2: Temperature Sensor Installation

    RC12 Series Ultrasonic Heat Meters   Notice: opening valve action should be slowly, to prevent water hammer effect during opening valve quickly, then damage heat meter and components. Temperature sensor installation During heat meter running, try to avoid valve closing Distinguish supply and back water completely in pipeline, to prevent heat meter freezing Temperature sensor of heat meter had each one...
  • Page 3 RC12 Series Ultrasonic Heat Meters   CAUTION • Tighten connection fittings by using two wrenches. Do not use calculator for support. Display This product uses button switch to switch LCD display interface, display content is following: • heat meter is installed on a vertical pipe, it is strongly a) After long press button 3 seconds, display menu will be recommended to install it on a flow against gravity as switched from three items A1-A2-A3.
  • Page 4 RC12 Series Ultrasonic Heat Meters   Error Codes Error Codes Fault information Prompt service incorrection flow Checking the flow or mounting err0____ direction or wrong direction;correction if necessary installation negative temperature Check the installation position of the err_1___ difference sensor; replace it if necessary Open circuit in flow err__2__ Repair or replacement by professionals...
  • Page 5 RC12 Series Ultrasonic Heat Meters   Short circuit in return err___5_ Repair or replacement by professionals temperature sensor err____6 Air tube Low battery Replace the battery Annex: 5 ...