MINIMUM PITCH
ONE IN. PER
10 FT OF LINE
BASE
RAIL
TO ROOF
DRAIN
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B
B-C
A-C
0.5
1 0
1 0
Fig. 3 — Unit Leveling Tolerance
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4-in trap is recommended.
Fig. 4 — External Trap Condensate Drain
NOTES-
1
Dimensions in ( ) are in miilimeters
2. Hook rigging shackles through holes in base rail, as shown in
detail "A" Holes in base rails are centered around the unit cen¬
ter of gravity. Use wooden top skid when rigging to prevent rig¬
ging straps from damaging unit
3. Unit weights do not include economizer. See Table 1 for econ¬
omizer weights.
A
CAUTION
All panels must be in place when rigging
MAX
DIMENSIONS
UNIT
WEIGHT
1
"A"
1
I
"B"
I
"C"
lb
kg
in.
mm
in.
mm
in.
mm
50LJ008
755
342
77 42
1967
40 25
1022
41.31
1050
50LJ009
760
345
77.42
1967
40 25
1022
41.31
1050
50LJ012
915
415
77.42
1967
40.25
1022
49.31
1253
50LJ014
930
422
77.42
1967
40 25
1022
49.31
1253
Fig. 5 - Rigging Details