Table 2 ~ Electrical Data
UNIT
50LJ
NOMINAL
VOLTAGE
(60 Hz)
VOLTAGE
RANGE
COMPR
(each)
OFM
IFM
ELECTRIC HEAT*
POWER SUPPLY
DISCONNECT SIZEf
Min
Max
RLA
LRA
FLA
FLA
Nominal
kW**
FLA
MCA
MOCPtt
FLA
LRA
008
(7V2
Tons)
208/230
{3-phase)
187
254
13.7
82
3.0
5 8
7.8/10 4
12 0/16 0
18 6/24 8
24.0/32 0
31.8/42 2
21 7/ 25 0
33 4/ 38 1
51 It 59 7
66 7/ 74 2
88 4/102.0
39 7/ 39 7
39 7/ 39 7
48 9/ 54 9
71 9/ 81 8
90 6/100 0
117 7/134 8
45/ 45
45/ 45
50/ 60
80/ 90(1
100/10011
125/150(1
42/ 42
42/ 42
45/ 50
66/ 75
83/ 92
108/124
223/223
460
(3-phase)
414
508
6.9
41
1 5
26
13.9
165
27 8
33 0
41.7
167
19.8
33 4
39 7
50 2
196
24 1
28 1
45 0
52 9
65 9
25
25
30
50
60
7011
21
22
26
38
46
58
112
575
(3-phase)
518
632
49
30
1 5
2.6
180
36 0
170
34.0
15 1
24 5
45 7
20
25
50
16
23
42
90
009
(8V2
Tons)
208/230
(3 phase)
187
254
162
84
30
5.8
7 8/10 4
12 0/16 0
18 6/24 8
24 0/32 0
31 8/42.4
21.7/ 25 0
33 4/ 38 1
51 7/ 59 7
66 7/ 74.2
88 4/102.0
45 4/ 45.4
45 4/ 45.4
48 9/ 54 9
71 9/ 81 8
90.6/100 0
117.7/134 8
|i
47/ 47
47/ 47
47/ 50
66/ 75
83/ 92
108/124
227/227
460
(3-phase)
414
508
8.0
42
15
26
139
16.5
27.8
33.0
41.7
16.7
19.8
33 4
39 7
50 2
22 1
24 1
28 1
45 0
52 9
65 9
25
25
30
50
60
70(1
23
23
26
38
46
58
114
575
(3-phase)
518
632
6 1
33
15
26
180
36 0
170
34.0
178
24 5
45 7
20
25
50
19
23
42
96
012
(10 Tons)
208/230
(3-phase)
187
254
192
105
30
58
7 8/10 4
12.0/16 0
24 0/32.0
31 8/42 4
37.5/50 0
21 7/ 25 0
33 4/ 38 1
66 7/ 74 2
88 4/102 0
104 1/120 2
52 1/ 52 1
52.1/ 52 1
52.1/ 54 9
90.6/100 0
117 7/134 8
137.4/127 4
60/ 60
60/ 60
60/ 60
100/100(1
125/15011
160/150(1
54/ 54
54/ 54
54/ 54
83/ 92
108/124
127/145
269/269
460
(3-phase)
414
508
96
55
1 5
26
165
27 8
33 0
41 7
50.0
198
33 4
39 7
50.2
60 1
■ '
25.7
28.1
45 0
52 9
65 9
63 4
30
30
50
60
70(1
70)1
27
27
41
46
58
69
140
575
(3-phase)
518
632
83
45
1.5
.
.
.
26
18.0
36.0
54 0
170
34 0
51 0
22 8
24 5
45 7
67 0
30
30
50
70(1
24
24
42
59
120
014
(12y2
Tons)
208/230
(3-phase)
187
254
22 3
137
30
120
7 8/10.4
12.0/16.0
24 0/32.0
31 8/42 4
37 5/50 0
21 7/ 25 0
33 4/ 38 5
66 7/ 77 0
88 4/102 0
104 2/120 3
65 3/ 65 3
65 3/ 65 3
65 3/ 65 3
98 4/111 2
125 5/142 5
145 3/135 3
80/ 80(1
80/ 8011
80/ 80(1
100/125)1
150/150)1
150/15011
69/ 69
69/ 69
69/ 69
91/102
115/131
134/152
376/376
460
(3-phase)
414
608
104
69
1 5
54
165
27 8
33 0
41 7
50 0
198
33 4
39 7
50 2
60 1
30 3
31 6
48 5
56 4
69 4
66 9
35
35
50
60
7011
8011
32
32
45
52
64
75
189
575
(3-phase)
518
632
96
55
1 5
54
180
36 0
54 0
170
34 0
51 0
28 5
28 5
49 2
70 5
35
35
50
80(1
30
30
45
65
161
LEGEND
FLA
HACR
IFM
LRA
MCA
MOCP
OFM
RLA
'Heaters are field installed only.
tUsed to determine minimum disconnect size per NEC
"Heater capacity (kW) is based on heater voltage of 240 v, 480 v or 575 v If power
distribution voltage to unit varies from rated heater voltage, heater kW will vary
accordingly
ttFuse or HACR circuit breaker
((Fusing in single point box provides the required branch circuit protection
NOTES;
1
In compliance with NEC requirements for multimotor and combination load equip¬
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for
the unit shall be fuse or HACR breaker The CSA units may be fuse or circuit
breaker
2 Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2% Use the following formula to determine the % voltage imbalance
% Voltage imbalance
max voltage deviation from average voltage
= 100
X
-;;-
average voltage
Full Load Anurs
Heating, Air Conditioning and Refrigeration
Indoor (Evaporator) Fan Motor
Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
Outdoor (Condenser) Fan Motor
Rated Load Amps
Example; Supply voltage Is 460-3-60
AB = 452
V
Determine maximum deviation from average voltage
(AB) 457 - 452 = 5
V
(BC) 464 - 457 = 7
V
(AC) 457 - 455 = 2
V
Maximum deviation is 7 v
Determine % voltage imbalance
7
% Voltage imbalance = 100 x-
= 1 53%
457
This amount of phase imbalance is satisfactory as it is below the maximum al¬
lowable 2%
IMPORTANT; If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately