3.2

Technical data

All values are typical values over the entire temperature range, unless stated otherwise.
EtherCAT
Connection
Electrical isolation
Supply voltages
Connection
U
nominal voltage
S
U
sum current: I
S
S,sum
Current consumption from U
Rated voltage U
P
U
sum current: I
P
P,sum
Current consumption from U
NOVRAM memory
Memory
Max. usable memory, cyclic access
Max. usable memory, acyclic access
Number of write/read
Housing data
Dimensions W x H x D
Weight
Installation position
Material
Environmental conditions
Ambient temperature during operation
Ambient temperature during storage
Vibration resistance, shock resistance
EMC immunity / emission
Protection class
Approvals/markings
*)
Approvals/markings 
*) Real applicable approvals/markings see type plate on the side (product marking).
Additional tests
The devices have undergone the following additional tests:
EP6080-0000
2 x M8 socket, 4-pin, A-coded, shielded
500 V
Input: M8 connector, 4-pin, A-coded
Downstream connection: M8 socket, 4-pin, A-coded
24 V
(-15 % / +20 %)
DC
max. 4 A
120 mA
S
24 V
(-15 % / +20 %)
DC
max. 4 A
None. U
P
128 kbyte NOVRAM
1280 bytes
up to 128 kbyte in max. 8190 byte sized objects, depending on
variable structure
variable
30 mm x 126 mm x 26.5 mm (without connectors)
approx. 165 g
variable
PA6 (polyamide)
-25 ... +60 °C
-25 ... +55 °C according to cURus
-40 ... +85 °C
conforms to EN 60068-2-6 / EN 60068-2-27
Additional tests [} 11]
conforms to EN 61000-6-2 / EN 61000-6-4
IP65, IP66, IP67 (conforms to EN 60529)
CE, cURus [} 21]
Version: 1.0
is only forwarded.
P
Product overview