(6) Obstructions on the left side, right side and rear side (Front side and above the unit are opened).
150 mm
or more
(7) Obstructions on the front side (Rear side, left side, right side and above the unit are opened).
150 mm
or more
(8) Obstructions on the front side and rear side (Left side, right side and above the unit are opened).
One of the obstructions' height shall be not more than 2000 mm.
250 mm
or more
*1
(9) Installation in front-rear rows
Installation with intakes facing intakes or outlets facing outlets (Left side, right side and above the unit are opened).
One of the obstructions' height shall be not more than 2000 mm.
300 mm
or more
(1500 mm
or more)
(10) In the case of continuous installation of the outdoor units, provide a space of 500 mm or more every three units for the
maintenance space.
250 mm
250 mm
or more*
or more*
150 mm
or more
250 mm
or more
2000 mm or more *
* The outdoor units require necessary space to unscrew on
the rear side for maintenance and if a sufficient maintenance
space is provided on the rear side (400 mm), the space of
250 mm
over 150 mm is enough at the right side.
or more*
* When using the air-discharge chamber : 500 mm or more
*1 The outdoor units require necessary space to unscrew on
*1
the rear side for maintenance and if a sufficient maintenance
space is provided on the rear side (400 mm), the space of
over 150 mm is enough at the right side.
*2 When using the air-discharge chamber : 1000 mm or more
(300 mm
or more)
* When using the air-discharge chamber : 1000 mm
500 mm
or more