Hitachi Central Station EX Installation Manual page 26

Air conditioner managing system
Table of Contents

Advertisement

(2) Modifi cation
* Setting modifi cation is needed for combined use with extension adapter.
It may take several minutes for the changes to take eff ect.
Do not set PIO01 IP address and PIO02 IP address.
24
1.
Tap panel for desired H-LINK No.
H-LINK No.00: Central Station EX
and embedded adapter
1
Other than H-LINK No.00: Extension
adapter
Modifi cation can be made only for
registered (green) panel.
2.
Tap [New registration/Edit].
If panel for H-LINK No.00 is selected,
step 3 is shown.
2
If panel for any other than H-LINK
No.00 is selected, step 5 is shown.
3.
Set network information for Central
Station EX.
Tap input fi eld for each item to enter
information on keyboard.
4
● If the network is exclusively for this
system, no setting change is necessary.*
3
4.
Tap [→] to confi rm setting and to go
to embedded adapter setting window.
5.
Tap input fi eld for each item to enter
information on keyboard.
Network information for embedded
adapter and extension adapter is in
6
the table on the previous page.
6.
Tap [ ] to confi rm setting and to
5
return to network window.
Tap [ ] to discard the change and to
return to network window.
Tap [←] to go to the previous page.
● Upon completing the setting, refer to "(1)
New registration" (page 22) and tap [
to register the contents.
]
A12124820A