AC•THOR / AC•THOR 9s / AC ELWA 2
If the RS485 communication connection on the meter is still being used by other devices,
communication with my-PV will not be possible!
A connection with the AC ELWA-E is not possible as it does not have Modbus RTU (RS485)
communication!
1. Default settings on my-PV device
Before commissioning, please read the installation instructions supplied with the device as well
as the operating instructions available online.
Find the AC•THOR operation manual here.
Find the AC ELWA 2 operation manual here.
We recommend installing the latest firmware on the AC-THOR via the Internet before
installation. IME is stored as a signal source from firmware version a0020708.
2. Communication with IME Conto D4
The combination with IME was tested by my-PV with IME Conto D4 Modbus MID.
According to IME, these types are compatible:
CE4TBDTMID
•
CE4TBDTCL1
•
CE4DF3DTMID
•
CE4DF3DTCL1
•
The my-PV device is connected directly to the meter via three-pole Modbus RTU cabling.
Use a shielded twisted pair cable and connect the shield to earth (GND) at one end!
RTU gateway should be equipped with a 120 Ohm terminating resistor!
AC•THOR / AC ELWA 2 with IME Conto D4 Modbus MID, Version 240115
Instructions for connecting
with IME Conto D4 Modbus MID
1