74
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
When the I/O Slave Station being set is registered in the Serial Master Station
(scan list registration), the I/O Slave Station must be re-registered in the Serial
Master Station after replacement, regardless of whether the serial number
check is enabled or disabled. Re-registration is not required, however, if the
serial number check is disabled and the model is the same as that being
replaced. To automatically register all I/O Slave Stations, turn OFF bit 8 of the
function setting switch (automatically register all I/O Slave Stations).
1. Before turning ON the power, set the function setting switch on the Serial
Master Station as follows:
Bit 7: ON (register scan list enabled)
ON
Bit 8: ON (register specified I/O Slave Station)
Bit 9: ON (serial number check enabled)
3 4
7 8 9 0
1 2
5 6
2. Set the node number of the I/O Slave Station to be connected using the
node setting switch.
W NODE
Setting range: 01 to 64
X10
X1
3. Set the frequency channel using the channel setting switch.
W CH
Setting range: 01 to 34, 51 to 83
X10
X1
4. Change the mode setting switch to SET mode, and then turn ON the pow-
er.
RUN
TEST
SET
5. Set the special function switch as follows:
ENTER
ON
OFF
6. The WS indicator will change from flashing green to being lit green when
scan list registration is completed.
Flashing green
WS
WS
7. Change the mode setting switch to RUN mode.
RUN
TEST
SET
OFF → ON → OFF
Lit green
Section 5-3