Daikin ComfortNet DX7TC Service Instructions Manual page 82

Split system heat pumps with r-410a refrigerant blowers, coils, & accessories
Table of Contents

Advertisement

SERVICING
READY DVPTC AIRFLOW TABLES
DIP SWITCH SETTING & AIRFLOW TABLE FOR ELECTRIC HEAT
HTR
S9
S10
S11
DV25PTCB14 DV29PTCB14
(kW)
3
ON
ON
ON
550
5
ON
ON
OFF
650
6
ON
OFF
ON
700
8
ON
OFF
OFF
800
10
OFF
ON
ON
850
15
OFF
ON
OFF
875
19*
OFF OFF
ON
NR
20
OFF OFF
ON
NR
21
OFF OFF
OFF
NR
25
OFF OFF
OFF
NR
NOTE: Airflow data shown applies to the electric heat only in either legacy mode or communicating mode operation
* Within thermostat user menu CTK0* communicating thermostat will display 20kW for OFF-OFF-ON dip switch selection,
21kW for OFF-OFF-OFF dip switch selection.
NR - Not Rated
** For match up with a 3 Ton outdoor unit:
Airflow for 5kW up to 15kW heater kits shall be set to 1300 cfm speed tap of ON-OFF-ON.
***For match up with a 3.5 Ton outdoor unit: Heater Kit application shall not exceed 20kW.
Airflow for 5kW heater kits shall be set to 1500 cfm speed tap of ON-OFF-OFF.
82
DV35PTCB14
DV33PTCC14
DV39PTCC14 DV49PTCC14
DV37PTCB14
550
550
600
NR
650
650
700
700
700
700
780
770
800
800
850
880
875
875
920
970
875
1050
950
1090
NR
NR
NR
1280
NR
NR
NR
NR
NR
NR
NR
NR
NR
NR
NR
NR
DV37PTCC14 DV59PTCC14 DV37PTCD14 DV59PTCD14 DV49PTCD14** DV61PTCD14*** DV31PTCC14
NR
NR
NR
NR
800
700
800
870
800
770
800
970
950
880
950
1060
1090
970
1090
1120
1290
1090
1290
1220
1345
1280
1345
NR
NR
NR
NR
1250
NR
NR
NR
NR
NR
NR
NR
NR
NR
NR
NR
990
950
1030
1110
1060
1150
1200
1150
1250
1240
1220
1320
1520
1520
1650
NR
NR
NR
1520
NR
1690
NR
NR
1750
NR
NR
1750
600
700
770
880
970
1090
1280
NR
NR
NR