Daikin ComfortNet DX7TC Service Instructions Manual page 63

Split system heat pumps with r-410a refrigerant blowers, coils, & accessories
Table of Contents

Advertisement

SERVICING
Run time f or last 4 cycles
is less than 3 minutes
each.
Compressor protector has
not tripped.
Low pressure and high
pressure switches are
closed.
Integrated control
module diagnostic/status
LED displ ay sho ws the
indicated code .
Compressor and outdoor
f
.
Compressor protector tr ips
four consecutiv e times .
Average r un time between
trips is less than 15
seconds .
Integrated control
module diagnostic/status
LED displ ay sho ws the
indicated code .
displa ys error message .
Compressor and outdoor
f
or greater than
4 hours .
Low pressure and high
pressure switches are
closed.
Integrated control
module diagnostic/status
LED displ ay sho ws the
indicated code .
displa ys error message .
Compressor and outdoor
f
.
Low pressure and high
pressure switches are
closed.
Integrated control
module diagnostic/status
LED displ ay sho ws the
indicated code .
displa ys error message .
Digit 3
Digit 2
Digit 1
0
3
Shor t Cycling
0
4
Loc ked Rotor
0
5
Open Circui t
0
6
Open Star t
Circuit
CMPR
03
Intermittent
SHR T
thermostat
CYCLE
demand.
Faulty
compressor
relay.
04
Compressor
R OTO R
bear ings are
seiz ed.
Failed
compressor r un
capacito r.
Faulty r un
capacitor wi ring.
Low line v oltage.
05
Po wer is
CIRCUIT
disconnected.
Failed
compressor
protector.
Compressor not
properly wired to
control.
06
Compressor star t
ST AR T
winding is open.
Failed
compressor r un
capacitor .
Faulty r un
capacitor wi ring.
Compressor not
properly wired to
control.
Faulty
compressor
wiring.
PCBHR104
Chec k ther mostat
Tu rn power OFF pr ior
and ther mostat
to repai r.
wiring; repair/
Fault will clear after 4
replace as
consecuti ve nor mal
needed.
cycles .
Chec k
Fault ma y be cleared
compressor
by cycling 24V AC to
relay operation;
control.
replace control as
Replace with correct
needed.
replacement par t(s).
Minimum compressor
runt time is changed
from 30 seconds to 3
minutes.
Chec k
Tu rn power OFF pr ior
compressor
to repai r.
operation; repair/
Must clear f ault by
replace as
cycling 24V AC to
needed.
control.
Chec k r un
Replace with correct
capacito r; replace
replacement par t(s).
as needed.
Chec k wiring;
repair/replace as
needed.
Ve rify line v oltage
is within range
on rating plate;
contact local
utility is out of
range .
Chec k circuit
Tu rn power OFF pr ior
break ers and
to repai r.
fuses .
Fault will clear after
Chec k wiring
normal cycl e.
to unit; repair/
Fault ma y be cleared
replace as
by cycling 24V AC to
needed.
control.
Chec k
Replace with correct
compressor ;
replacement par t(s).
repair/replace as
needed
Chec k
compressor
wiring; repair/
replace as
needed.
Chec k
Tu rn power OFF pr ior
compressor ;
to repai r.
repair/replace as
Fault will clear after 1
needed.
normal cycl e.
Chec k r un
Fault ma y be cleared
capacito r; replace
by cycling 24V AC to
as needed.
control.
Chec k wiring;
Replace will correct
repair/replace as
replacement par t(s).
needed.
1
63