Daikin ComfortNet DX7TC Service Instructions Manual page 64

Split system heat pumps with r-410a refrigerant blowers, coils, & accessories
Table of Contents

Advertisement

SERVICING
Compressor and outdoor
f
.
Low pressure and high
pressure switches are
closed.
Open star t circuit has been
detected 4 times with 5
minute delay between each
detection.
Integrated control
module diagnostic/status
LED displ ay sho ws the
indicated code .
displa ys error message .
Compressor and outdoor
f
.
Low pressure and high
pressure switches are
closed.
Integrated control
module diagnostic/status
LED displ ay sho ws the
indicated code .
displa ys error message .
Compressor and outdoor
f
.
Low pressure and high
pressure switches are
closed.
Open r un circuit has been
detected 4 times with 5
minute delay between
each detection.
Integrated control
module diagnostic/status
LED displ ay sho ws the
indicated code .
displa ys error message .
Air conditioner/heat
pump may appear to be
operating nor mally.
Compressor protector ma y
be open (compressor and
outdoor f
Integrated control
module diagnostic/status
LED displ ay sho ws the
indicated code .
64
Digit 3
Digit 2
Digit 1
L
6
Open Star t
Circuit
Loc kout
0
7
Open Run
Circuit
L
7
Open Run
Circuit
Loc kout
L
8
Low Line
Voltage
06
Compressor star t
ST AR T
winding is open.
Failed
compressor r un
capacitor .
Faulty r un
capacitor wi ring.
Compressor not
properly wired
to control.
Faulty
compressor
wiring.
07
Compressor r un
winding is open.
Compressor not
properly wired
to control.
Faulty
compressor
wiring.
07
Compressor r un
winding is open.
Compressor not
properly wired
to control.
Faulty
compressor
wiring.
08
Low line v oltage.
VO LT
PCBHR104
Chec k
Tu rn power OFF pr ior
compressor ;
to repai r
repair/replace as
Must clear f ault by
needed.
cycling 24V AC to
Chec k r un
control.
capacitor ; replace
Replace with correct
as needed.
replacement par t(s).
Chec k wiring
repair/replaced
as needed.
Chec k
Tu rn power OFF pr ior
compressor ;
to repai r.
repair/replace as
Fault will clear after 1
needed.
normal cycl e.
Chec k wiring;
Fault ma y be cycling
repair/replace as
24V AC to control.
needed.
Replace with correct
replacement par t(s).
Chec k compres -
Tu rn power OFF pr ior
sor ; repair/re-
to repai r.
place as needed.
Must clear f ault by cy -
Chec k wiring;
cling 24V AC to control.
repair/replace as
Replace with correct
needed.
replacement par t(s).
Chec k circuit
Tu rn power OFF pr ior
break ers and
to repai r.
fuses .
Control detects line
Ve rify unit is
voltage less than
connected to
185 VAC.
power supply
Fault will clear if line
voltage increases
rating plate .
above 185 VAC.
Correct lo w line
voltage condition;
contact local
utility if needed.