ABB AKD-5 Installation Manual page 30

Entelliguard retrofill circuit breakers
Table of Contents

Advertisement

Figure 26. Example Wiring Diagram for AK25 Secondary Disconnects and Photo Example
Below are tables
(Table 9
and Table10) featuring the two 39-blocks (A and B). They make up the 78-point secondary-
disconnects.
NOTE:
For Shunt trip > 125Vdc only: Use 2 NO contacts in series with coil.
For S/T #1 use 2nd NO contact at terminals B25-B26. (Jumper A21 to B25 and B26 to A5.).
For S/T #2 use 2nd NO contact at terminals B17 -B18. (Jumper B20 to B17 and B18 to A12
).