Automatic Stop; Storage; Recording A Measurement - AEMC 6418 User Manual

Clamp-on ground resistance tester
Hide thumbs Also See for 6418:
Table of Contents

Advertisement

3.6 AUTOMATIC STOP

After 5 minutes of inactivity, the instrument enters to standby mode. Press any
key or turn the switch to any setting to exit standby. The instrument restarts
without repeating the calibration procedure if it has not been on standby for more
than 15 minutes. It is possible to disable automatic standby; refer to § 3.4 (STOP
menu). The

3.7 STORAGE

3.7.1 Recording A Measurement

To record a measurement, PRESS the MEM key.
You can first PRESS the HOLD key to freeze the measurement.
18
When the impedance measurement is > 1200 Ω, the
instrument displays OR.
When the current measurement is > 20 A, the
instrument so indicates.
When the impedance measurement is < 1 Ω, the
display alternately indicates the measured value and
LOOP, indicating the value is very low for a valid
ground impedance measurement and most likely
indicates the measurement is through a wire loop
rather than through the earth.
symbol is then displayed.
Clamp-On Ground Resistance Tester Model 6418 - User Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

2141.03

Table of Contents