Table 5 — Electric Data for All Voltages and for Units With or Without Electric Heat
42WKN
SUPPLY
NOMINAL
VOLTAGE
CAPACITY
(DIGIT 8)
(DIGIT 6, 7)
A: 115/60/1
J: 110/50/1
B: 208/60/1
08 and 12
Small Chassis
C: 230/60/1
K:220/50/1
H: 277/60/1
A: 115/60/1
J: 110/50/1
18 and 20
B: 208/60/1
Medium
C: 230/60/1
Chassis
K: 220/50/1
H: 277/60/1
A: 115/60/1
J: 110/50/1
B: 208/60/1
30 and 36
Large Chassis
C: 230/60/1
K: 220/50/1
H: 277/60/1
TERMINAL STRIP CONNECTIONS
INSTALLATION
The terminal strip connections are designed to clamp down on the
incoming building power and thermostat wiring connections. To
properly connect the wires to the terminal strip:
1.
Push a small flat head screwdriver into the square hole on
the terminal. Press firmly until the screwdriver hits the
back stop and opens the terminal. See Fig. 45.
2.
Remove approximately 3/8 in. (9.5 mm)of insulation from
the end of the wire and push the stripped wire into the oval
hole in the terminal.
3.
Remove the screwdriver. Pull on the wire to make sure
that it is securely clamped in the terminal.
4.
Make sure that the terminal clamp is in contact with bare
wire (insulation removed).
Fig. 45 — Terminal Strip
PERFORMANCE (WITH ELECTRIC HEAT)
RECOMMENDED
FLA
MCA
6.2
7.8
6.9
8.6
6.6
8.2
12.3
15.4
13.6
17.0
13.0
16.3
20.8
26.0
22.9
28.6
22.0
27.4
PERFORMANCE (NO ELECTRIC HEAT)
FLA
FUSE SIZE
0.7
15
15
0.3
15
0.3
1.1
20
20
0.6
20
0.5
2.2
30
30
1.1
30
0.9

Disconnect Switch

For models with a factory installed disconnect switch (Digit 12 =
D), the switch will be installed on the side of the control panel. See
Fig. 46 and Fig. 2-4 dimensional drawings for the location of the
control panel on the unit.
Fig. 46 — Factory Installed Disconnect Switch
Refer to Fig. 47-52 for typical 42WKN unit wiring diagrams.
46
RECOMMENDED
MCA
FUSE SIZE
0.9
15
0.4
15
0.4
15
1.4
15
0.7
15
0.6
15
2.8
15
1.4
15
1.1
15