SPECIFICATIONS
Power
Operating range
Communication
Onboard Sensors
Inputs
(7C-HS-C2W-X)
Power Source: 24V AC/DC input (+/- 15%)
Peak consumption: 1.4VA Maximum
Temperature 32 to 122°F (0°C to 50°C)
Humidity 20-85% non-condensing.
Sensor bus for daisy chained sensor communication and low power 3V dc.
4-wire interface for RS 485 communication @ 115200 baud and 5V
DC, 100mA power source
900-928 MHz Mesh IEEE 802.15.4-compliant, for communications to CCU
Bluetooth: BLE 4.1 for commissioning, and communication to wireless sensors
Temperature range of 32 to 122°F with an accuracy of +/-1°F
Humidity 0 to 100% with an accuracy of 2%
CO2 sensor with a range of 0 - 40,000 ppm, accuracy of +/-30ppm
VOC sensor; Typical Accuracy: 15% of measured value; TVOC: 0 - 60,000
ppb;
Occupancy sensor based on passive infrared (PIR) with a detection range of
4m with a 15-degree angle
Light Sensor. Ambient light sensor • <100 LUX resolution • High-accuracy UV
index sensor • Matches erythermal curve
Sound sensor with 40-120dB response for 100Hz to 10KHz
PM2.5, PM10 sensor (optional). Detection range of 0-1000µg/m3 and accuracy
of +/-10µg/m3 (PM2.5, 0-100µg/m3) or +/-25µg/m3 (PM10, 0-
100µg/m3). Maximum long-term mass concentration precision limit drift:
•
0 to 100 µg/m3 ±1.25 µg/m3/year
•
100 to 1000 µg/m3 ±1.25 % mV/year
2 x 10K Type-2 thermistor inputs with 2% accuracy
2 x 0-10V Analog voltage inputs with 2% detection accuracy (2-10V)
Touch slider for temperature control along with 3 mechanical buttons