Eaton ESR5-BWS-31-24VDC Manual page 35

Safety relays for emergency stop, protective door and light grid monitoring
Table of Contents

Advertisement

LED
State
Power
K1
K2
The sensor circuit is active. The
reset/start circuit (S34) is/was
activated. Both safety circuits
K1 and K2 are not picking up
The sensor circuit is active. The
reset/start circuit (S34) is/was
activated. The safety circuit (K1)
does not pick up.
The sensor circuit is active. The
reset/start circuit (S34) is/was
activated. The safety circuit (K2)
does not pick up.
Legend: ○ – LED off, ● – LED on
Possible cause
S34 manual reset error 
(stuck-at on input).
External error:
The sensor circuit channels were not both
opened / requested.
Internal error:
Diagnostics active.
External error:
The sensor circuit channels were not both
opened / requested.
Internal error:
Diagnostics active.
ESR5-BWS-31-24VDC 11/23 MN049020EN Eaton.com
4 Maintenance
Remedy
Fix the problem in the reset/start circuit.
Then carry out a functional test.
External error: 
Check whether the second channel is
opened with the sensor's request.
Internal error: 
Perform a power-down reset followed by a
function test. If the error occurs again
after the function test, replace the
device.
External error: 
Check whether the second channel is
opened with the sensor's request.
Internal error: 
Perform a power-down reset followed by a
function test. If the error occurs again
after the function test, replace the
device.