Download Print this page

CENTRAL ULTRA K-25 ESFR Manual

Low pressure early suppression fast response

Advertisement

Quick Links

C:ENTR
ULTRA™ K-25™
1-99
ULTRA™ K-25™ ESFR
Lo\N Pressure
Early Suppression
Fast Response
Manufactured by: Central Sprinkler Company
451 North Cannon Avenue, Lansdale. Pennsylvania 19446
Product
Description
The Central ULTRA™ K-25,.,, Early
Suppression Fast Response (ESFR)
Automatic Sprinkler has been de-
signed to meet high challenge fire
hazards while eliminating the high
pressure requirements of K-
i
4 ESFR's
and the need for in-rack sprinklers.
The Model
UL
TRA'"K-25n' uses a
larger orifice than other ESFR sprink-
lers which allows the reduction of the
required pressure The pressure re-
quired varies
by
building and storage
height. Refer to the required pressure
chart for specific requirements.
The ULTRA™
K-25™
has several ad-
vantages over 14 K-Factor ESFR's.
The main advantage Is in the lower
required pressure. This reduction, up
to 60% in some cases, can have a
dramatic effect on the sprinkler system.
It can
eliminate
the need for a pump
and all of the associated pump ex-
pense, such as additional electrical
service to the building. The maximum
deflector distance Is 18"
(457 2 mm)
compared to 14"
(355.6 mm)
as is the
case for 14 K-factor ESFA's, and the
reduction in pressure can make instal-
lation
more cost effective
with
smaller
easier to install
pipe. Another
main
advantage is that the UL TAN"' K-2S™
is for buildings up to 45'-0"(13. 7
m)
high
with
40'-0"r12.2
mJ of storage
without
the need for in-rack sprinklers.
14
K-Factor
ESFA's
require in-rack sprin-
klers
discharging
at 50 psi
in
this situa-
tion. Eliminating in-rack sprinklers in
situations where
14 K-Factor
ESFA's
can not, shows the outstanding perfor-
mance of the ULTRA"• K-25"''
The Model ULTRA',..K-25™ utilizes a
160°F/ 71°C or a 200°F/ 93°C Fast
Response element, giving the sprinkler
the required fast response characteris-
tics.
The
fast response, combined
with water droplet size and velocity
provide early suppression to high
challenge fires.
Operation:
The ULTRA™ K-25™ uti-
lizes a heat sensitive three fin operat-
ing element. It does not use an o-ring
in
any part of the design. The element
operates when heat Is absorbed by
the heat fins and conducted
to
the
alloy pellet. At the rated temperature
the alloy pellet melts, causing the ball
plunger to drop, freeing balls from the
retaining groove. This releases the
heat fin/ washer assembly
and
allows
the arms to eject and the water to
flow from the open orifice.
-
ATTENTION -
ULTRA™ K-25™ ESFR'S
have a 1"
(25 mm)
thread. Be sure to list/
order the correct outlet
on the branchline.
Early
Suppression
Fast
Response
Automatic
Sprinkler
~
Technical
ill~
Data
Model: UL TAN .. K-25r"
Style: Pendent
Orifice Size: .930
(23.6 mm)
K-Factor:
25.2
(360.5
metric)
Thread Size: 1" N.P.T
(25 mm)
Temperature Rating: 160°F/ 71
°c
200°F/ 93°C
Sensitivity: Quick
Response
Approvals: FM
Maximum Working Pressure:
175 psi
(12.1 bar)
Factory Hydro Test:100% at
500
psi
(34.5 bar)
Standard Finish: Brass
Length: 4 1/a''
(105 mm)
Width: 2
13 /,5"
(71 .4
mm)
Weight: 11 oz.
(313 g)
Patents: Patents are pending.
No. 3•1.0

Advertisement