Download Print this page
CENTRAL ELO-231 Manual

CENTRAL ELO-231 Manual

Specific application .6 density/2,000 sq. ft.

Advertisement

Quick Links

ELO-231
Specific Application
.6 Density/2,000 sq. ft.
Manufactured by: Central Sprinkler Company
451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Product
Description
The Central Model ELO-231 Automatic
Sprinkler is an Extra Large Orifice Sprinkler
that has been proven for storage occupancies
by full-scale fire testing at Factory Mutual and
designed to control high challenge fires in
storage occupancies with relatively low
required operating pressures. The
ELO-231 x
1
" is now available in a glass bulb
2
design, as well as the traditional center strut
design. It is available in the standard
thread in upright and pendent, and for retrofit
use a
1
" thread is available for upright only.
2
Through additional full-scale fire tests at
Factory Mutual, the ELO-231 has been U.L.
Listed and Factory Mutual Approved to
reduce the required remote area for Class I
through IV commodities and Group A Plastics
(see table) to 2,000 sq. ft. This represents up
to a 50% decrease in area when using
Central's ELO-231 sprinkler. Never has a
orifice standard spray sprinkler received such
recognition for its performance in full-scale fire
testing.
The decrease in remote area, results in a
dramatic reduction of the required water flow
demand. This, combined with the low
operating pressure requirements, results in:
• The ability to store higher when compared
to
1
" and
17
" standard spray sprinklers at
2
32
the same flow demand. This is because
standard spray sprinklers require higher
water flow demands to protect the same
height of storage.
• More water pressure is made available by
reducing the overall water demand of the
system. For example, a .6/4000 sq. ft.
demand of NFPA 231C would normally
require a minimum of 2,400 GPM. The
ELO-231 reduces this area to a .6/2,000 sq.
ft. demand or 1,200 GPM. The available
water pressure is higher at 1,200 GPM than
at 2,400 GPM. Therefore, there is higher
available pressure for use in hydraulic
calculations.
* NFPA 231, 231C and 231D applications require 10
psi; 7 psi can be used for NFPA 13 applications.
• Flexibility for spec-occupancies by allowing
palletized or rack storage of Class I through
IV commodities and Group A plastics up to
20' (see application chart on page 2). This
provides owners and tenants great
flexibility in allowable storage arrange-
ments, heights and commodities.
The low end head pressures of the 11.4
K-factor, combined with the increase of
pressure available by reduced area, results in
the ability to:
• Reduce Pipe Size
• Increase Spacing
• Eliminate Booster Pumps
3
"
• Upgrade Existing Densities
4
Technical
Data
Model: ELO-231 or ELO-231 x
Style:
Upright or Pendent
not available in
5
"
Orifice Size: 0.64"
8
K-Factor: 11.4
(163.02)
3
Thread:
"
(19.1 mm)
4
Temperature and Color:
Glass Bulb
155°F/68°C - Red
200°F/93°C - Green
286°F/141°C - Blue
Approvals: U.L., U.L.C, F.M.,
*MEA (127-93-E) (See chart on
page 3 for specific temperatures
and finishes.)
* MEA Approved for 165 ° F & 286 ° F center strut
upright only.
Minimum Operating Pressure:
Maximum Working Pressure:
Factory Hydro Test: 100% at 500 psi
Standard Finish: brass, chrome
Corrosion Resistant Coatings: See Page 3.
3
Length: 3
"
(8.1 cm)
16
3
Width: 1
"
(4.5 cm)
4
Weight: 4.8 oz.
(136 grams)
Head Guard: G-2 (U.L. Listed for Upright only
& F.M. Approved for Upright &
Pendent)
ELO-231SA
1
"
2
(pendent
1
" thread)
2
(E.L.O.)
(16.3 mm)
Nominal
1
or
"
N.P.T.
(12.7 mm)
2
Center Strut
165°F/74°C - Uncolored
212°F/100°C - White
286°F/141°C - Blue
*10 PSI
(68.95 kpa)
175 psi
(12.07 bar)
(34.48 bar)
1-97
O P
T
I M
ELO-231
.64 Orifice
Automatic
Sprinkler
No. 2-9.2
A

Advertisement

loading

Summary of Contents for CENTRAL ELO-231

  • Page 1 Factory Hydro Test: 100% at 500 psi Sprinkler (34.48 bar) require a minimum of 2,400 GPM. The Standard Finish: brass, chrome ELO-231 reduces this area to a .6/2,000 sq. Corrosion Resistant Coatings: See Page 3. ft. demand or 1,200 GPM. The available Length: 3 ⁄...
  • Page 2 NOTE: The ELO-231 is a standard spray sprinkler for use with the area/density curves of the NFPA standards and a specific application sprinkler for reduced area. The following guidelines are only for reduced area applications. These guidelines do not apply if you are not using the ELO-231 for reduced area specific application. For standard applications, see the ELO-231 data sheet not this specific application data sheet.
  • Page 3 Figure 3 Figure 4 ⁄ " thread must only be used on ELO-231 S.A. GB Upright Sprinkler ELO-231 S.A. GB Pendent Sprinkler retrofit applications. Factory Mutual's Loss Prevention Data Sheets contain the requirements for designs that differ from NFPA. Product Description 3 3/16"...
  • Page 4 Do not attempt to reassemble or of the warranty. Step 3. Hand tighten the sprinkler into otherwise reuse a sprinkler that has the fitting. Use a Central ELO Sprinkler Ordering operated. Replace any sprinkler exhibiting Wrench, to tighten the unit into the fitting.