CENTRAL ESFR-1 Quick Start Manual

Early suppression fast response pendent automatic sprinkler

Advertisement

Quick Links

ESFR
Early Suppression
Fast Response
Pendent Automatic Sprinkler
Manufactured by: Central Sprinkler Company
451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Product
Description
The Central Model ESFR-1 Early
Suppression Fast Response
Automatic Sprinkler has been
designed to meet high challenge fire
hazards.
The Model ESFR-1 utilizes a
160°F/71°C or a 212°F/100°C Fast
Response solder link, giving the
sprinkler the required fast response
characteristics.
The fast response, combined with
water droplet size and velocity
provide early suppression to high
challenge fires.
The ESFR-1 is approved for use with
storage up to 35 feet in 40 foot
buildings and 25 feet in 30 foot
buildings, as referenced in the NFPA
Standards, Underwriter's
Laboratories and Factory Mutual's
installation standards.
A head guard is available for use with
the ESFR-1. It must be assembled at
the factory, so be sure to specify it
when ordering.
Technical
Data
Model: ESFR-1
Style:
Pendent
Wrench: ELO/ESLO/ESFR-1
Combination
Orifice Size: 0.69"
K-Factor: 14.0
3
Thread Size:
/
" N.P.T.
4
Temperature Rating: 160°F/71°C.
212°F/100°C
Approvals: U.L., U.L.C., F.M., M.E.A.
(424-93-E-ESFR-1)
Maximum Working Pressure: 175 psi
Factory Hydro Test: 100% at 500 psi
Standard Finish: Brass
3
Length:
4
/
"
4
Width:
2
3
/
"" (frame arms)
4
Weight:
8.2 oz.
Patents:
Patents are pending.
ESFR-1
E a r l y
S u p p r e s s i o n
F a s t
R e s p o n s e
A u t o m a t i c
S p r i n k l e r
3 - 9 6
No. 2-13.0

Advertisement

loading

Summary of Contents for CENTRAL ESFR-1

  • Page 1 Factory Hydro Test: 100% at 500 psi Standard Finish: Brass The ESFR-1 is approved for use with Length: " storage up to 35 feet in 40 foot buildings and 25 feet in 30 foot Width: ""...
  • Page 2 ESFR-1 Early Suppression Fast Response Pendent Sprinkler 2-3/4" 1-15/16" 3/4" NPT 4-3/4" Note: All ESFR-1 Sprinklers are factory shipped with protective cardboard guards. DO NOT REMOVE IT PRIOR TO SPRINKLER INSTALLATION. AFTER SPRINKLER INSTALLATION, BE SURE TO REMOVE IT.
  • Page 3 Design Requirements — Applications Because the discharge pattern is critical to protection of life and The design and installation of ESFR-1 sprinkler systems must comply with the property, nothing should be hung or applicable standards of NFPA, Underwriter's Laboratories, the Authority Having...
  • Page 4 U.S. and Canada, and internationally, through a network of Central Sprinkler distribution centers. You may write directly to Central Sprinkler Company, or call (215) 362- 0700 for the distributor nearest you. Patents: Patents are pending.