Product
Description
The Central Model ELO-16 GB FR Extra
Large Orifice Automatic Glass Bulb Upright,
Pendent and Recessed Pendent Sprinklers
are designed for Extended Coverage spacing
in Ordinary Hazard occupancies per NFPA 13
with very low pressure required.
The ELO-16 GB FR (upright and pendent)
is the first extended coverage ordinary hazard
sprinkler ever Approved by Factory Mutual.
As with any project that requires Factory
Mutual Approval, always consult the F.M.
Guidelines for their specific requirements.
The Model ELO-16 GB FR incorporate a
specially designed deflector that provides a
much greater area of coverage than most
commercial sprinklers. The extra large orifice
allows this greater area of coverage, while
requiring much lower pressure.
The ELO-16 GB FR are intended for use,
as all extended coverage sprinklers are, with
hydraulically designed systems and using the
flows and pressures as shown in this bro-
chure. All spacing is rounded up to the next
higher category. For example, 17'-6" x 15'-0"
spacing would be calculated at the Listed 18'
x 18' flow and pressure.
Operation: The glass bulb capsule
operating mechanism contains a heat-
sensitive liquid that expands upon application
of heat. At the rated temperature, the
frangible capsule ruptures, thereby releasing
the orifice seal. The sprinkler then discharges
water in a pre-designed spray pattern to
control or extinguish the fire.
Installation Limitations:
• Unobstructed or non-combustible
obstructed construction*
• Minimum hydraulic design area of 5
heads or 1500 sq. ft., whichever is
greater.
• Minimum spacing between sprinklers is
12' for upright and 12'-6" for pendent.
* WEB members of open WEB trusses must not exceed
1" diameter. Maximum ceiling slope of 2" per foot.
ELO-16 GB FR OH
Technical
Data
Model: ELO-16 GB FR
Style:
Upright, Pendent and Recessed
Pendent
Escutcheon: Model ELO Recessed
(2-piece)
Note: For the recessed configuration,
only the Model ELO Recessed 2-piece
Escutcheon may be used. Substitution
of other "recessed" escutcheons may
impair the operating sensitivity and
distribution pattern. For the pendent
version, non-recessed escutcheons such
as the Model 401 may be used, but are
not required.
Wrench: ELO/ESLO/ESFR Combination
(upright and pendent) Part #1073
ELO Offset (recessed pendent)
Part #1092
Orifice Size: 0.64"
(16.3 mm)
K-Factor: 11.4
(163.02)
Thread Size:
3
" N.P.T.
(19.1 mm)
4
Temperature Rating & Glass Bulb Color:
Ordinary
155°F/68°C
Intermediate
200°F/93°C
High
250°F/121°C
Approvals: U.L., **F.M.,
M.E.A. (466-92-E Vol. II)
**Upright & Pendent only, not recessed pendent.
Maximum Working Pressure: 175 psi
Factory Hydro Test: 100% at 500 psi
Standard Finishes: brass, chrome plated
Decorative Coatings (F.M.) : white or
black painted
Corrosion-Resistant Coatings (F.M.) :
wax, lead, wax-over-lead
Corrosion-Resistant Coatings (U.L.) :
white or black painted
Escutcheon: brass, chrome plated, white
or black painted
Length:
3
1
"
(7.94 cm)
8
Width:
2"
(5.08 cm)
Weight:
5.0 oz.
(142 grams)
Response: Standard
O P
(ELO)
Red
Green
Blue
Extended
Coverage
Ordinary Hazard
Upright, Pendent
& Recessed
Pendent Sprinkler
11-95
T
I M A
No. 3-3.1

Advertisement

loading

Summary of Contents for CENTRAL ELO-16 GB FR OH

  • Page 1 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 Product Technical Description Data Model: ELO-16 GB FR The Central Model ELO-16 GB FR Extra Large Orifice Automatic Glass Bulb Upright, Style: Upright, Pendent and Recessed Pendent and Recessed Pendent Sprinklers Pendent are designed for Extended Coverage spacing...
  • Page 2 ELO .64 1 7/8" Diamater 2" Diameter Note: Central's Model 65 or 401 escutcheon may be used. When using Central's Model 65 escutcheon, the face of R.C. is to protrude 1/8" ±1/16" beyond the finished ceiling line. ELO-16 GB FR Extended Coverage Ordinary Hazard Recessed Pendent 1"...
  • Page 3 Installation Design Data All Central Model ELO-16 GB FR For FM Projects Automatic Glass Bulb Sprinklers must be installed according to current NFPA Consult the Factory Mutual Guidelines for 13 Standards and these installation instructions. Deviations from these specific Factory Mutual requirements if Factory requirements and standards or any Mutual Approval is required.
  • Page 4 Any Central Sprinkler distribution centers. ties Having Jurisdiction , and notify all sprinklers altered in such manner You may write directly to Central personnel who may be affected must be replaced. Sprinkler Company, or call (215) 362- during system shutdown.