Download Print this page
CENTRAL tyco CHEC Quick Start Manual

CENTRAL tyco CHEC Quick Start Manual

8.0 k-factor concealed horizontal extended coverage quick response light hazard, sidewall sprinklers

Advertisement

Quick Links

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Model CHEC — 8.0 K-factor
Concealed Horizontal Extended Coverage
Quick Response Light Hazard, Sidewall Sprinklers
General
Description
The 8.0 K-factor, Model CHEC (Con-
cealed Horizontal Extended Cover-
age), Quick Response Light Hazard,
Sidewall Sprinklers are decorative, 3
mm bulb type sprinklers featuring a
unique cover plate designed to con-
ceal the sprinkler. It is the best choice
for architecturally sensitive areas such
as dormitories, hotel rooms, reception
areas, office buildings, banquet facili-
ties, conference rooms, and hospitals.
The soft contour of the cover plate
optimizes a low profile while blending
in with surrounding surfaces. The
plate, while maintaining a fast re-
sponse sensitivity has been specifi-
cally designed without vent holes to
increase its aesthetic appeal while
helping to avoid objects from being
hung from the sprinkler (i.e., garment
bags, clothes hangers, etc.) that might
otherwise cause an inadvertent opera-
tion.
They are designed for installation
along a wall or the side of a beam and
beneath a smooth and level ceiling.
Horizontal sidewall sprinklers are com-
monly used in lieu of pendent or up-
right sprinklers because of aesthetics
or building construction considera-
tions where piping across the ceiling is
not desirable.
They are intended for use in automatic
sprinkler systems designed in accord-
ance with standard installation rules
(e.g., NFPA 13) for light hazard occu-
pancies. The fast response thermal
sensitivity rating of the Model CHEC
Sprinklers provides for a quick re-
sponse extended coverage rating up to
a 16 ft. x 22 ft. coverage area.
Each unit includes a Cover Plate As-
sembly that conceals the sprinkler op-
erating components. The separable
two-piece design of the Cover Plate
and Support Cup Assemblies allows
installation of the sprinklers and pres-
Page 1 of 6
sure testing of the fire protection sys-
tem prior to the installation of the wall
or application of a finish coating.
Also, the separable "push-on and
thread-off" two-piece design of the the
Sprinkler provides for 1/2 inch (12,7
mm) of horizontal adjustment.
The Model CHEC Sprinklers are
shipped with a Protective Cap. The
Protective Cap is temporarily removed
for installation, and it can be replaced
to help protect the sprinkler while the
wall is being plastered, wallpapered,
or painted. When the wall installation is
complete the Protective Cap is re-
moved and the Cover Plate Assembly
installed.
WARNINGS
The Model CHEC (Concealed Hori-
zontal
Extended Coverage), Quick
Response Light Hazard, Sidewall
Sprinklers described herein must be
installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
National Fire Protection Association,
in addition to the standards of any
other authorities having jurisdiction.
Failure to do so may impair the integ-
rity of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
Sprinkler
Identification
Number
TY4332 - ECLH HSW, 8.0K, 3/4"NPT
JANUARY, 2003
Customer Service/Sales:
Tel: (215) 362-0700 / (800) 523-6512
Fax: (215) 362-5385
Technical
Data
Approvals
UL and C-UL Listed.
(The listings apply only to the service
conditions indicated in the Design Cri-
teria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
1/2
K = 8.0 GPM/psi
(115,2 LPM/bar
Temperature Ratings
135°F/57°C Sprinkler with 135°F/57°C
Cover Plate
155°F/68°C Sprinkler with 135°F/57°C
Cover Plate
Adjustment
1/2 inch (12,7 mm)
Finish
Cover Plate: Bright White or Chrome
Plated. (Custom colors other than
white are available on special re-
quest.)
Physical Characteristics
Frame . . . . . . . . . . . . Bronze
Button . . . . . . . . Bronze/Copper
Button Spring . . . . Stainless Steel
Sealing Assembly . . . . . . . . . .
. . . . . . Beryllium Nickel w/Teflon†
Bulb, 3 mm Diameter . . . . . Glass
Close
1/2
)
TFP265

Advertisement

loading

Summary of Contents for CENTRAL tyco CHEC

  • Page 1 Close Customer Service/Sales: Tel: (215) 362-0700 / (800) 523-6512 Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Fax: (215) 362-5385 Model CHEC — 8.0 K-factor Concealed Horizontal Extended Coverage Quick Response Light Hazard, Sidewall Sprinklers sure testing of the fire protection sys- General tem prior to the installation of the wall or application of a finish coating.
  • Page 2: Operation

    Page 2 of 6 TFP265 SUPPORT CUP RETAINER COVER PLATE COVER WITH ROLL FORMED FRAME DEFLECTOR WITH THREAD EJECTION PLATE THREADS DIMPLES SPRING WRENCH FLATS 3/4" NPT BUTTON SEALING PUSH INTO ASSEMBLY BUTTON SUPPORT CUP COMPRESSION EJECTION BULB UNTIL RETAINER SOLDER SCREW SPRING...
  • Page 3 TFP265 Page 3 of 6 SPRINKLER MANUFACTURER COVER PLATE SUPPORT CUP PRESET GAP RETAINER ASSEMBLY 5/32" (4,0 mm) ASSEMBLY TOP OF DEFLECTOR 7/16" (11,1 mm) 2-3/8" to 2-5/8" DIA. 3-5/16" DIA. (60,3 to 66,7 mm) (84,1 mm) WRENCH CENTERLINE FLATS OF SPRINKLER WATERWAY 1/2"...
  • Page 4: Care And Maintenance

    Page 4 of 6 TFP265 Response Coverage Minimum Minimum Deflector- Sprinkler Lateral Rating Area Flow Pressure To-Ceiling Temperature Minimum Ft. x Ft. (m x m) GPM (LPM) PSI (BAR) Distance , In. (mm) Rating, °F Spacing Ft. (m) Quick 16 x 14 (4,9 x 4,3) 26 (98) 10.6 (0,73) 4 to 12 (100 to 300)
  • Page 5: Limited Warranty

    TFP265 Page 5 of 6 Sprinklers that are found to be leaking Limited Ordering or exhibiting visible signs of corrosion must be replaced. Warranty Procedure Automatic sprinklers must never be painted, plated, coated or otherwise Products manufactured by Tyco Fire When placing an order, indicate the full altered after leaving the factory.
  • Page 6 Page 6 of 6 TFP265 TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446...