QUALITROL AKM345 GEN3 OTIWTI
40-08847-00-Rev001
40024
R/W
8.3.5
MODBUS Notes
Special Transformer Temperature Values:
•
The application will display the temperature value as 555°C if valid dial selection is not done.
•
If the temperature value goes 2°C or more down below the dial lower range, the application will display
temperature as -999°C.
•
If the temperature value goes 2°C or more above the dial upper range, the application will display
temperature as 999°C.
9. Troubleshooting
9.1 Matching Resistance
•
Be sure to check the input current being used is steady.
•
Be sure to check the proper resistance is set on the internal matching resistance.
•
Be sure to wait 45 minutes before reading the winding temperature gradient.
9.2 Remote Outputs
•
Ensure proper supply voltage is being used.
•
Check wiring as wiring arrangement may differ depending on features.
www.qualitrolcorp.com
TM
Instruction Manual
[ Note: Device will set the new system time after
the MSB register is written. Writing Only LSB
register will not change the system time in the
device. ]
16Bit unsigned int
Reserved