Matching Resistance; Power - Qualitrol OTIWTI AKM345 GEN3 Instruction Manual

Winding temperature indicator
Table of Contents

Advertisement

QUALITROL AKM345 GEN3 OTIWTI
40-08847-00-Rev001
5.3.3

Matching Resistance

To utilize the internal matching resistance of the AKM345 GEN3, you must connect your bushing CT directly to
the unit.
The CT input for the AKM345 GEN3 is designated on the terminal blocks as follows:
5-5 = primary matching resistance (applicable to TD50, TD76, and TD50(5A))
56-57 = secondary matching resistance (applicable to TD50(X2) and TD76(X2))
NOTE: terminal block arrangement may differ depending on other options selected, but terminal
designation will remain the same
5.3.4

Power

In some configurations, the AKM345 GEN3 will require a power input for the remote indication or Modbus
communication.
he power inputs will be identified with a "+" and "-" for positive and negative respectively.
The input power requirement is 24VDC.
www.qualitrolcorp.com
TM
Instruction Manual
Matching Resistance Wiring Example