Facp Input Set Up Procedure - Fail-Safe Installation - Honeywell MPA2C3 Installation Manual

Access control unit
Hide thumbs Also See for MPA2C3:
Table of Contents

Advertisement

FACP input activated: Doors 1 to 2/4 are and stay in unlocked state, and controls
are not possible using cards, egress or software/Web User Interface.
Note: See the MPA2C3 installation manual how to connect the Fire panel output to the
MPA2C3 in chapter 4.6 , and how to connect the outputs the to fail safe locking
devices (power-to-lock), with the correct jumper settings of (OUT1, OUT3 (AUX1),
OUT2, OUT4 (AUX2)).
Note: Jumper head on FACP jumper needs to be
Note: off when the FACP input is in use and to un-bypass the FACP input.
Note: *Fail safe locking devices (power-to-lock) are devices that unlock when power
(voltage) is interrupted to the locking device. This interruption can be done by
opening a NC (Normally Closed) contact of a relay (door) output via the controls of
the panel or when power to the panel or to the locking device is lost. Main examples
for fail safe locking devices are magnetic locks.
FACP input set up procedure – FAIL-SAFE INSTALLATION
The below procedure is to create a fail-safe installation. Any diversion from these
steps will make the installation not fail-safe (unlock doors at power fail and at
FACP input triggered).
To make sure all door outputs are in a fail-safe mode, the panel needs to be in
Reversed Door Access Mode. The are 5 steps to make the FACP input fully func-
tional.
Set panel in Reversed Door Access Mode
In Panel configuration/advanced/FACP Input:
Go to section DOOR OUTPUT OPERATION:
1. Select DOOR ACCESS MODE: REVERSED
118
MPA2C3 Installation Guide