Honeywell MPA2C3 Installation Manual page 48

Access control unit
Hide thumbs Also See for MPA2C3:
Table of Contents

Advertisement

(2 door)
Reader mode
MPA2C3-4
(4 door)
Reader mode
OSDP
The 2 RJ45 reader terminals (READER1 IN/OUT or READER1/3) on the left lower
side can be simultaneously set to Wiegand or OSDP mode. Both DIP Switch SW1
bit1 (OSDP1) AND Jumper RDR 1(/3) have to be set to the correct positions for the
required Wiegand or OSDP reader mode.
In OSDP mode the RS485 termination can be set by DIP Switch SW2 Bit 1&2 (EOL
OSDP1). See
42
MPA2C3
RJ45 Connector
READER
READER 1 IN
Wieg.A/ OSDP 1
READER 1 OUT
Wieg.B / OSDP 1
OSDP
READER 2 IN
Wieg.A / OSDP 2
READER 2 OUT
Wieg.B / OSDP 2
RJ45 Connector
READER
READER 1
Wieg.A / OSDP 1
READER 2
Wieg.A / OSDP 2
READER 3
Wieg.A / OSDP 1
READER 4
Wieg.A / OSDP 2
OSDP Bus termination
OSDP Reader
Reader Address
Reader Function
1
Door1 IN reader
2
Door1 OUT reader
1
Door2 IN reader
2
Door2 OUT reader
OSDP Reader
Reader Address
Reader Function
1
Door1 IN reader
2
Door1 OUT reader
1
Door2 IN reader
2
Door2 OUT reader
3
Door3 IN reader
4
Door3 OUT reader
3
Door4 IN reader
4
Door4 OUT reader
(page 55).