OSDP mode panel setting

The MPA2C3 2-door system OSDP mode can manage up to 4 readers to support 2
doors with IN and OUT readers per door.
The OSDP readers are connected to the panel's AES encrypted OSDP protocol (v
2.x). The OSDP reader are connected to the panels bus (OSDP1 or OSDP2). OSDP
readers must have an address to get the proper function. The combination OSDP
bus (1 or 2) and the address of the reader determines the function of the reader for
which door. See table below.
In OSDP mode more than one reader can be connected to an OSDP RS485 bus.
To set up the MPA2C3 in OSDP mode per door DIP Switch.
Table 3-4 DIP Switch settings and Jumpers
MPA2C3-4 (4
door)
1. * OSDP Readers must be addressed to achieve required function
2. ** SW2: Bit 1 and 2 must be set synchronized for OSDP 1 bus;
3. *** RDR 1 (JP13/JP14) and RDR 2 (JP15/JP16) both jumpers must be set
Once the reader terminals have been set to OSDP mode correctly, the two LEDs on
the RJ45 connector will have the following function:
Left yellow LED: OFF
Right green LED
46
OSDP1 is one RS485 OSDP bus with RJ45 terminals READER1 IN and
READER1 OUT
OSDP2 is one RS485 OSDP bus with RJ45 terminals READER2 IN and
READER2 OUT
DIP Switch
Reader mode
OSDP
Bit 1: ON
(OSDP1)
Bit 10: ON
(OSDP2)
SW2: Bit 3 and 4 must be set synchronized for OSDP 2 bus
synchronized
OSDP reader not connected: OFF
Valid OSDP reader connected to panel: flashing
SW1
SW2**
Bit 1&2:
(EOL OSDP1)
Bit 3&4:
(EOL OSDP2)
Jumpers***
RDR 1/3
RS485 Termination Enable 2-3
OFF: NO EOL
(OSDP 1)
ON : EOL
RS485 Termination
OFF: NO EOL
ON : EOL
MPA2C3 Installation Guide
RDR 2/4
Enable 2-3
(OSDP 2)