Pressure Curves

COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB
TEMPERATURE, OUTDOOR TEMPERATURE, DISCHARGE AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1);
LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN.
EXAMPLE: (1) OUTDOOR TEMP. 82 F.
(2) INDOOR WET BULB 67 F.
(3) AT INTERSECTION
(4) DISCHARGE PRESSURE @ 800 CFM CFM IS 333 PSIG.
(5) SUCTION PRESSURE @ 800 CFM CFM IS 141 PSIG.
18-EB40D1-1E-EN
Figure 9. Pressure Curve – 4YCC4024E1
Cooling
INDOOR ENTERING
500
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG
450
400
(3)
(3)
(4)
(4)
350
300
250
(1)
200
40
60
80
OUTDOOR TEMPERATURE (Degree F)
170
170
INDOOR ENTERING
INDOOR ENTERING
165
165
WET BULB CURVES
WET BULB CURVES
TOP TO BOTTOM
TOP TO BOTTOM
160
160
71, 67, 63 AND 59
71, 67, 63 AND 59
DEG F.
DEG F.
155
155
150
150
145
145
140
140
(5)
(5)
135
135
130
130
125
125
120
120
115
115
(1)
(1)
110
110
40
40
60
60
80
80
OUTDOOR TEMPERATURE (Degree F)
(2)
100
120
(2)
(3)
(3)
100
100
120
120
ACTUAL:
DISCHARGE PRESSURE SHOULD BE +/- 10 PSI OF CHART
SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
U U n n i i t t S S t t a a r r t t u u p p
Dwg. 4YCC4024E1
29