Users Manual

Auxiliary Input

The Logger supports up to two additional measurement channels with
either the wired AUX input or wireless radio signals from Fluke
Connect sensors.
Wireless Connection to Fluke Connect Modules
The Logger supports wireless radio communication with Fluke
3000-series modules to remotely monitor equipment. See Figure 10.
Wireless communication requires that the USB-1 FC WiFi-BLE
adapter or Bluetooth adapter is installed. See WiFi and WiFi/BLE-to-
USB Adapter on page 4 for more information.
To set up a module:
1.
Turn on the module.
2.
Push
on the module to turn on the radio. The display shows
.
3.
On the Logger, select AUX 1 or AUX 2. Active FC sensors within
a 10 m range show in the selection list on the Logger. Highlight
the FC module and push
to the module.
30
. The Logger assigns an ID number
4.
Verify on the module:
ID number shows on the module
flashes to confirm the connection
FC modules that are connected to another device are not
available and do not show in the selection list.
5.
Verify that the Measurement Configuration screen shows the ID
number and module type in the AUX field.
If the module moves out of range, the ID number does not
show in the Measurement Configuration screen to indicate that
the connection is broken. The connection is re-established when
the module moves back into range.
6.
On the Logger, go to the Meter screen to view the measurements
from the connected module.
You cannot change the measurement parameter or unit on
the module during a logging session.
For more information about FC module support with the Logger, go to
www.fluke.com.
Note
Note