Riello RS 70/EV Installation, Use And Maintenance Instructions page 26

Forced draught gas burners
Table of Contents

Advertisement

Example
Maximum output required: 2000 MBtu/hr
Ring nut 2) (Fig. 16) adjusted as in the diagram of Fig. 15
Gas pressure at output of 2000 MBtu/hr
Pressure in combustion chamber
1.97 + 1.18
pressure required at pressure test point 1) (Fig. 21).
p "wc gas butterfly 2)
RS 70/EV
MBtu/hr
kW
1586
465
1757
515
1928
565
2098
615
2269
665
2440
715
2610
765
2777
814
2951
865
RS 100/EV
MBtu/hr
kW
2644
775
2878
843
3125
916
3371
988
3616
1060
3863
1132
4109
1205
4405
1291
RS 130/EV
MBtu/hr
kW
3521
1032
3825
1121
4129
1210
4432
1299
4736
1388
5036
1476
5340
1565
5545
1625
20029395
Installation
=
1.97 "wc
=
1.18 "wc
=
3.15 "wc
p "WC
0.1
0.1
0.1
0.1
0.1
0.2
0.2
0.2
0.2
p "WC
0.3
0.4
0.4
0.5
0.5
0.7
0.7
0.9
p "WC
0.6
0.7
0.9
1.0
1.1
1.3
1.4
1.6
RS 70/EV
RS 100/EV
RS 130/EV
D2441
24
Burner output operation
Burner output operation
Burner output operation
1
2
D3123
Fig. 21
Fig. 22

Advertisement

Table of Contents
loading

Table of Contents