ABB UniGear ZS2 Installation, Operation And Maintainance Instructions page 45

Table of Contents

Advertisement

An additional mechanical switching device for
manual operation of the circuit breaker in the
Service position is also installed (see Fig. 26, 27).
If the withdrawable part is in the Service position,
operation is carried out using the knob which
swings a push rod extension out. (see Fig. 26, 27).
Figure 59 - Earth switch with key-lock arrangement
Left-top: Earth switch Maneuver position indicator as should be seen
on front
Right - bottom: Earth switch position indicator as should be seen from
lower window
7
Key lock*for Earth switch at open position
8
Key lock* for Earth switch at closed (earthed) position
9
Key lock* to prevent CB racking-in
10+11
Handle-cover to open entrance for operating lever
12+13
Earth switch operating lever (Art.No: 143429-802)
*Key-locks are optional. Lock by rotating the key 180º clockwise.
It is possible to remove the key only at locked position.
8.3.3 Earthing switch - type EK6
The earthing switch EK6 has a snap closing
mechanism which is independent of the rotation
of the drive shaft. An earthing switch allocated to
a circuit breaker is enabled for switching only
when withdrawable part is in the Test/
Disconnected position or removed from the
switchgear. Turn earthing switches ON only when
the doors are closed.
45