Bosch CLIMATE 5000 VRF BMS-LON Installation And User Manual page 12

Building management system gateway card (lonworks)
Hide thumbs Also See for CLIMATE 5000 VRF BMS-LON:

Advertisement

12 | NETWORK VARIABLE CHARTS
Output network variables (n:1~32, air conditioner address:32~63)
NO
Meaning
1
setting Temperature
nvoSetTemp[n]
2
Indoor Temperature
nvoIndoorTemp[n]
3
Error protection
nvoWorkState[n]
4
Operation state
6 720 862 467 (2017/05)
Name
Type
SNVT_temp_p
SNVT_temp_p
SNVT_state_64
NvoWork
SNVT_hvac_
ModeFan[n]
status
Definition
17.00=17℃
18.00=18 ℃
19.00=19℃
20.00=20℃
21.00=21℃
22.00=22℃
23.00=23℃
24.00=24℃
25.00=25℃
26.00=26℃
27.00=27℃
28.00=28℃
29.00=29℃
30.00=30℃
17.00=17℃
18.00=18℃
19.00=19℃
20.00=20℃
21.00=21℃
22.00=22℃
23.00=23℃
24.00=24℃
25.00=25℃
26.00=26℃
27.00=27℃
28.00=28℃
29.00=29℃
30.00=30℃
Bit0
Phase error or no phase
Bit1
Communication error
Bit2
T1 sensor error
Bit3
T2 sensor error
Bit4
T2B sensor error
Bit5
T3 or T4 or digital compressor discharge
temperature sensor error
Bit6
Zero crossing detection error
Bit7
EEPROM error
Bit8
Fan speed detection out of control
Bit9
Comm. error(main board and display board)
Bit10
Compressor over cureent (4 times)
Bit11
Inverter module protection
Bit12
Fresh error
Bit13
Outdoor unit error protection
Bit14
Water level detection error
Bit15
Other errors
......
Bit48
Evaporator temperature protection
Bit 49
Anti-cold air or defrosting protection
Bit 50
Condenser high temperature protection
Bit 51
Compressor temperature protection
Bit 52
Discharge pipe temperature protection
Bit 53
Discharge high pressure protection
Bit 54
Discharge low pressure protection
Bit 55
Power over voltage protection
Bit 56
Compressor over current
Bit57
Reserve, stay 0
Bit58
Reserve, stay 0
Bit59
Reserve, stay 0
Bit60
Reserve, stay 0
Bit61
Reserve, stay 0
Bit62
Reserve, stay 0
Bit63
Other errors
* Other positions are default to be 0
HVAC_AUTO
HVAC_HEAT
MODE
HVAC_COOL
HVAC_FAN ONLY
HVAC_OFF
0.005
HIGH
0.010
MED
Fan_output
0.020
LOW
0.000
AUTO
0 Communication success
1 Communication consequential failure 1 time
2 Communication consequential failure 2 times
3 Communication consequential failure 3 times
4 Communication consequential failure 4 times
5 Communication consequential failure 5 times
In_alarm
6 Communication consequential failure 6 times
7 Communication consequential failure 7 times
Communication consequential failure 7
times,the value 1 will re-calculate until
communicationsuccess, and then this value
will be zero;
Specifications
Display the setting
temperature
Display indoor temperature
0~15 positions means error
state
48~63 positions means
protection state
Initial value
Heat Mode
Cool Mode
Fan only Mode
OFF Mode
Display the operating mode,
indoor fan and communication
quality, mode is applied to the
operating mode, fan_output
is applied to fan state,
in_alarm is applied to the
communication quality