Introduction; Installation - Bosch CLIMATE 5000 VRF BMS-LON Installation And User Manual

Building management system gateway card (lonworks)
Hide thumbs Also See for CLIMATE 5000 VRF BMS-LON:

Advertisement

1.

INTRODUCTION

1.1.
APPLICATIONS
For the connection between the central A/C system and the Building
Management System (BMS) (namely Automated Building System)
with LonWorks® interfaces by realisng the integration of A/C system
and Building Management system.
1.2.
FEATURES
Connect the central A/C system to LonWorks® network.
Comply with LonMark® Standard, gateways is a intelligent node
base on LonWorks® technique.
The core control module of node apply Flash Memory, which
application program could be downloaded on line.
Connect to LonWorks® network by twisted pair line, and the
communication mode is nonpolar.
Provide with a LonWorks® control interface for BMS by network
variables complying with LonMark® standard.
LonWorks® interoperability Guidelines Version 3.4 Compliance
LonWorks gateway between LonMark/LonTalk® protocol and MDPP
(Private protocol).
The gateway can convert the lonTalk protocol to the MDPP protocol.
Connection to 64(MAX) indoor units.
Valid address for each unit: 0x00~0x3F.
1.3.
SPECIFICATIONS
Indoor and Ventilator Function Block
Monitoring
On/Off status report
Running Mode status report
Fan Speed status report
Set Temp. value report
Indoor temp. value report
Error status report
Online/Offline status report
Quality of Connection status
report
CLIMATE 5000 VRF
Controlling
Mode Setting for single unit
Mode Setting for all units
Stop Setting for single unit
Emergency Stop for all unit
Fan Speed Setting for single unit
Fan Speed Setting for all unit
Temp. Setting for single unit
Temp. Setting for all unit
Technical Specifications
NO. FUNCTION
DESCRIPTION
1
Processor
Neure chip, 10MHz, 64K Flash memorizer
• Hidden operation switch
• Operation LED (Red)
2
Functions
• Power LED(Green)
3
Transceiver
FTT-10A+isolating transformer
• Voltage range : 100-240VAC
4
InputPower
• MAX Current:200 mA
• temperature:0-50°C
Operation
5
ambient
• Relative humidity:25-90%
• LonMark standard allocative attribute
Software
• Support Direct-Memory reading and
6
configuration
writting by the LNS network management
tool.
Communication
Rs485 connector for MD-Net
7
port
LonWorks FT-10 connector for LNS
8
Size
31.9cm X 25.1cm X 6.1cm
* FT-10 line is used to connect LNS and BMS-LON gateway for
LonWorks
2.

INSTALLATION

2.1.
ILLUSTRATION
SWITCH POWER
INTRODUCTION | 3
To LonWorks
To Indoor units
Centralized Controls
POWER
AC 220V
6 720 862 467 (2017/05)