Inst allat ion of Elect ric Auxiliary Heat M odule
(f or some models)(not supplied)
Accessories
Name
Owner's and Installation
manual
Seal sponge
Screw
Rubber cap
Electric auxiliary heating
wiring diagram
Air switch label
NOTE:
Installation must be performed by an authorized
dealer or specialist. Please make necessary
protection when installing the unit.
Speci cation series of electric auxiliary heat module:
3kW,5kW,8kW,10kW, 15kw, 20kW,25kW.
The electric auxiliary heat module is only used
for installation on the AHU internal machine.
If the unit needs to be equipped with electric
auxiliary heat module, please check the electric
auxiliary heat module speci cation that can be
matched with the unit rst to avoid unnecessary
consequences caused by improper matching.
Selection and matching of internal machine and
electric auxiliary heating components
M ODEL
3kW
5kW
8kW
(Bt u/ h)
12K
Y
Y
Y
18K
Y
Y
Y
24K
-
Y
Y
30K
-
Y
Y
36K
-
Y
Y
48K
-
-
Y
60K
-
-
-
www.hvacmirage.us
Shape
Quant it y
1
1
7
1
1
1
10kW
15kW
20kW
25kW
-
-
-
-
Y
-
-
-
Y
Y
-
-
Y
Y
-
-
Y
Y
Y
-
Y
Y
Y
-
Y
Y
Y
Y
Inst allat ion Requirement s
Before installation, please check the list of electric
auxiliary heat modules and physical objects. After
transportation, check whether the electric heating
is damaged. If any damage is found, please contact
the after-sales personnel immediately.
Elect ric Auxiliary Heat M odule inst allat ion
and w iring operat ion
1. Remove the upper cover and use professional
tools to destroy the knock-out holes of the
upper cover.