N2-B6 Series - 8/23/23
Reset MENU Password
If you forgot the main menu password, you can reset the menu password to default password "4321" by entering a correct
active code.
Exit Tool Mode
Press key [F3] to return to monitoring mode.
Menu "1_SYSTEM SETUP"
The system setup subdivision contains general settings for monitor operations, communications and 4-20mA calibrations.
Password:
Default password is 4321.
MAC
The B6 RS-485 address can be defined from 0 to 255. B6 default address is 126.
Address:
Object ID:
BACnet Device Instance Number. Default is 4005.
Baud rate:
Define baud rate for RS-485 communication with BACnet protocol. B6 default baud rate is 38400 bps.
In normal operation, the sensor and relay status information scrolls automatically. Set the number of
Scroll Rate:
seconds for each item to be displayed. Default value is 3 seconds.
The LCD backlight can be set to Always Off, Always On and Auto Power Saving mode. In Auto Power
Backlight:
Saving mode, the backlight will turn on for 10 seconds after any key has been pressed. Default setting
is Auto.
The B6 supports the execution of the TimeSynchronization service and UTCTimeSynchronization
UTC Offset
service. It indicates the number of minutes ( - 780 to +780) offset between local standard time and
Universal Time Coordinated. Default is +300 (US & Canada Eastern Time).
It indicates whether daylight saving time is in effect (Enabled) or not (Disabled) at the B6 location
in UTCTimeSynchronization service.
Daylight Saving
Default is Enabled.
The new password can be any combination of up to four digits. Default password is 4321.
New Password:
Warning:
Protocol:
The B6 supports BACnet MS/TP master or slave protocol. Default is MS/TP master.
Display Instant: displays instantaneous gas concentration
Display Average:
Displays STEL (15min average reading)
Displays TWA (8 hour average reading)
Displays daily peak
Display Alarm: displays alarm 1-8 status
Display Mode:
Display Relay: displays relay 1-3 status
Display Buzzer: displays buzzer 1-3 status
Display A-Out mA: Not Available for B6
Display A-Out VDC: Not Available for B6
Display Clock: displays real time clock (Default is no clock display) If there is nothing to display, the unit
will display "Running..."
Catalog No. 11-808-788-01
Be sure that you record the new password in a safe and secure location!
Specifications subject to change without notice.
Toxic/Combustible Gas Transmitter B6
Installation and Operation
Page 9 of 16