Function and Configuration

Indicators
The indicators consist of five LED's – two to indicate RS-485 digital communication, three to indicate the status of relays 1-
3.
RS485-TX/RX:
When the B6 is connected to a controller system via RS-485, the traffic of the communication
can be monitored visually through the two RS-485 indicators. One is RX LED, which indicates
the data stream received in from the controller. The other is TX LED, which indicates the data
stream out of the B6.
Note: If the TX LED or the RX LED is always ON, is indicative of a communication problem.
See Troubleshooting for RS-485.
Relay 1-3 LED:
Indicate the status of each relay. When the relay is actuated/closed, the relay LED is ON. When the relay is de-
actuated/open, the relay LED is OFF.
Note: If you set the relay to be Normally Energized (Fail Safe), the relay LED will turn ON at non-alarm state and turn OFF
at alarm state, because the LED reflects the relay coil status.
Tool Function
Press key [F3] to enter tool functions that might be used
frequently in the field.
Enter Main Menu
Press key [F1] to browse previous item of the current
menu.
Press key [F2] to browse next item of the current menu.
Press key [F3] to enter the main menu for more
configuration and settings.
Hush Buzzer and Relay
Press key [F3] to silence the buzzer and buzzer-style
relays.
Reset Latched/Hushed
To acknowledge a latched condition or a hushed condition,
press key [F3] to reset latched relays and hushed buzzer
for which the alarm condition has been removed. If the
alarm condition (e.g. high gas concentration) is still
present the relay(s) will not reset.