Toxic/Combustible Gas Transmitter B6
Installation and Operation
N2-B6 Series - 8/23/23
Menu "4_OUT TEST"
During system installation and testing, it may be necessary to force relays and buzzers on and off.
The Relay Testing feature allows the user to force the actuation of each relay. This function forces an Actuate vs. De-
actuate action, not an energized vs. non-energized action. Therefore the user must be aware of these relays, which have
been defined as normally energized or not normally energized.
According to UL2075 standard for safety, the Q6 Endurance Test will automatically perform 6000 cycles of Relay/Buzzer
On and Off operation at a rate of not more than 15 cpm.
Note: The 4mA and 20mA outputs are not available for Q6.
Menu "5_VIEW SETTING"
This function is to verify the settings for the alarms, relays, buzzers and analog outputs. Note: The View of A-Out Setup is
not available for B6.
Specifications subject to change without notice.