N2-B6 Series - 8/23/23
Menu "6_ALARM SETUP"
First to select which sensor's alarm is going to be set, B6M or Q6R? The subsequent alarm settings will be performed on
that sensor. The B6M supports alarm 1 to alarm 8 on its sensor. The Q6R supports alarm 1 to alarm 8 on its sensor too.
Alarm is a programmable condition that can receive a selectable input and trigger relays and buzzers.
Disabled or
Each alarm may be individually set to be enabled or disabled. If the alarm is disabled, the
Enabled:
alarm will not be used to calculate or trigger anything.
Default: Alarm 1 to Alarm 4 is enabled. Alarm 5 to Alarm 8 is disabled.
Input:
One of five inputs is selected to calculate the alarm condition status to trigger the
selected outputs:
Catalog No. 11-808-788-01
INSTANT: instantaneous gas reading.
15 MIN AVG (STEL): Short Term Exposure Limit, average reading over 15
minutes.
8 HOURS AVG (TWA): 8-hour Time Weighted Average, average reading over 8
hours.
DAILY PEAK: daily peak reading.
FAULT: If the unit reports any faults, no matter the gas concentration, it will
trigger the selected outputs.
Specifications subject to change without notice.
Toxic/Combustible Gas Transmitter B6
Installation and Operation
Page 13 of 16

Advertisement

Table of Contents
loading