N2-B6 Series - 8/23/23
Alarm On
If Alarm On is greater than or equal to Alarm Off:
and Alarm
Alarm On: Sets the concentration at or above which the relay will actuate.
Off
Alarm Off: Sets the concentration at or below which the relay will de- actuate.
Reading:
If Action On is less than Action Off:
Action On: Sets the concentration below that the relay will actuate. Action Off: Sets the
concentration above that the relay will de-actuate.
Trigger:
Trigger Outputs: Relay 1, Relay 2, Relay 3, Buzzer 1, Buzzer 2, Buzzer 3
Menu "7_RELAY STYLE"
Enabled:
Each relay may be individually set to be enabled or disabled. If it's disabled, the relay will
always de-actuate no matter what the current gas concentration.
Default is Enabled.
Normally De-
Each relay may be individually set to be normally energized or normally de-energized.
energized:
Default is normally de-energized.
Latching:
Each relay may be set to latch in actuate status until acknowledged by a front-panel action.
Default is Non-Latching.
ON Delay:
"Delay on Actuation" or "Delay on Make". For each relay a separate time delay may be set
from 0 to 990 seconds before an alarm condition will cause the relay to actuate.
Default is 5 seconds.
OFF Delay:
"Delay on De-Actuation" or "Delay on Break". For each relay a separate time delay may be
set from 0 to 990 seconds before a return to a non- alarming signal condition will cause the
relay to de-actuate.
Default is 5 seconds.
Style:
Normal Relay Style: Work as normal relay.
Buzzer Style Relay: When the relay is used to control a buzzer or horn. Working as a buzzer
style will make the relay have the same function as the buzzer. It will be switched off when
performing the Hush Buzzer/Relay function in the Tool Menu.
Default is OFF.
Menu "8_BUZZER STYLE"
The buzzer style is almost identical to that of the relays, except the style that represents the buzzer tone options:
• Tone 1: Chirp once.
• Tone 2: Chirp twice.
• Tone 3: Intermittent 50% duty cycle.
• Tone 4: Continuous.
The menus are identical to those for the Relay Style.
Menu "A_ALL DISABLE"
This function is for calibration, system testing etc. When All Disable is ON, the status of the relay, buzzer and analog
output, etc., will freeze in their current state.
Default is OFF.