Carrier B6 Series Specification page 15

Toxic/combustible gas transmitter
Table of Contents

Advertisement

N2-B6 Series - 8/23/23
Menu "B_SIMULATION"
First to select B6M or Q6R to be set into simulation mode
Simulation mode is used to assist in testing the installation before commissioning. When simulation is enabled, the unit will
not detect gas concentrations; it will display the simulated value and use it to calculate the status of relays and buzzers.
This feature is available for evaluating the user settings and testing the installation (e.g.: the activation of the valve, fan
speed, relay set points, etc. can be verified.)
Any concentration between 0ppm and 9999ppm can be simulated.
Menu "C_SITE SERVICE" and "D_FACTROY SET"
Factory service staff access only. The customer has no need to operate it.
BACnet PIC Statement Supported By B6
See document: 86650-103-000 (B6 PIC Statement).
Smart Sensor Assembly Replacement
Disassembling
Observe all safety and electrical codes and regulations before removing enclosure lid.
Calibrate the transmitter whenever a component is replaced. But if you replace a smart sensor
assembly with a sensor onboard, you don't need to recalibrate the transmitter, as all the calibration
Tip
information has been stored in the smart sensor board in the factory process.
Replacement Procedure
To replace the entire smart sensor assembly, complete the following steps:
Catalog No. 11-808-788-01
Specifications subject to change without notice.
Toxic/Combustible Gas Transmitter B6
Installation and Operation
Page 15 of 16