QBM4000-1
QBM4100-1D
QBM4000-3
QBM4000-10
QBM4000-25
Degree of protection
Connections
Environmental conditions
Directives, standards
Environmental compatibility
Dimensions (weight)
5/6
Siemens
Smart Infrastructure
Zero point
Sum from linearity, reproducible and hysteresis.
TC zero point
TC sensitivity
Zero point
Sum from linearity, reproducible and hysteresis.
TC zero point
TC sensitivity
Zero point
Sum from linearity, reproducible and hysteresis.
TC zero point
TC sensitivity
Long-term stability
Response time
Load change
Tolerable overload on one side
.
on P1
At P2
Rupture pressure
at room temperature
at 70 °C
Display (QBM4100-1D only)
Display of:
Media
Admissible medium temperature
Maintenance
Protection degree of housing at recommended
installation
Protection class
Electrical connections
Pressure connections
Permissible ambient temperature
Operation
.
Transport and storage
Permissible ambient humidity
Product standard
EU Conformity (CE)
RCM Conformity
The product environmental declaration CE1E1916*) contains data on environmentally compat-
ible product design and assessments (RoHS compliance, materials composition, packaging,
environmental benefit, disposal).
Weight (with packaging)
Weight (with packaging), with display
*) The documents can be downloaded from http://siemens.com/bt/download.
Differential pressure sensor QBM4000.../ QBM4100...
<±1.0 % FS
<±1 % FS
<±0.1 % FS/°C
<±0.06 % FS/°C
<±0.7 % FS
<±1 % FS
<±0.05 % FS/°C
<±0.05 % FS/°C
<±0.7 % FS
<±1 % FS
<±0.04 % FS/°C
<±0.02 % FS/°C
±1.0% FS as per DIN IEC 60 770
< 2 0 ms
<10 Hz
5,000 Pa
(10,000 Pa for types QBM4000 -10, -25)
400 Pa
2 × overload
1.5 × overload
LCD, 2-line, 8 position each, alphanumeric, not
background lit

Differential pressure in Pa
Air and slightly aggressive gases
.
0...70 °C
Maintenance free
IP54 according to EN 60529
III according to EN 60730-1
3-pin round plug with screw terminals 1.5 mm
(Lumberg RKC 30 / 11)
PVC nipples
designated as 'P2' or ' – '
0...70 °C
-25...+ 70 °C
< 90 % r.h. (without condensation)
EN 61326-1
Electrical equipment for measurement,
control and laboratory use. EMC require-
ments. General requirements
CE1T1910xx_01
CE1T1910en_C1
UL 60730-1 / UL 60730-2-6,
http://ul.com/database
0.250 kg (with round plug connector).
0.263 kg (with round plug connector).
.
6.2 mm, under pressure side is
.
.
*)
*)