Download Print this page

Siemens QBM4000 Series Quick Start Manual page 4

Differential pressure sensor

Advertisement

Commissioning notes
Caution
Sensor calibration
Disposal
Technical data
Power supply
QBM4000-...
3-wire connection
QBM4000-...
2-wire connection
Product data
QBM4100-1U
4/6
Siemens
Smart Infrastructure
The values indicated under "Technical data" apply only to vertically mounted differ-
ential pressure sensors (connection nipples pointing down).
The sensor is calibrated at the factor in the vertical position. As a consequence, the
sensor must be installed in the vertical position. For horizontal installation (hous-
ing cover top or bottom), deviations occur to measured values that negate the
measured values on the certificate.
The device is considered electrical and electronic equipment for disposal in terms
of the applicable European Directive and may not be disposed of as domestic gar-
bage.
• Dispose of the device via the channels provided for this purpose.
• Comply with all local and currently applicable laws and regulations.
Operating voltage
Power consumption
Current draw
External supply line protection
Output signal
Operating voltage
for ohm loads up to 500 Ω
Power consumption
Current draw
Output signal
Measuring range
Sensing element
Degree of measuring accuracy at required
installation position and room temperature
25 °C.
Sum from zero point, linearity, reproducible
and hysteresis.
TC zero point
TC sensitivity
Differential pressure sensor QBM4000.../ QBM4100...
Safety extra low voltage (SELV/PELV)
or class 2 (UL)
AC 24 V ± 15 %, 50 / 60 Hz or DC 13.5...33
< 0.5 VA
< 10 mA
Fuse slow max. 10 A
or
Circuit breaker max. 13 A
Characteristic B, C, D according to EN 60898
or
Power source with current limitation of max. 10 A
DC 0...10 V, R Last > 10 k
separated, 3-wire connection, short-circuit proof,
protected against reverse polarity)
DC 8...33 V
.
DC 18...33 V
< 0.7 VA
4...20 mA
4...20 mA
supply vol
<
R
load
2-wire technology, short-circuit proof, protected
against reverse polarity)
Refer to "Type summary"
Piezo-resistive (silicone membrane, ceramic bar)
(FS = Full Scale)
<±1 % FS (<±1 Pa)
<±0,1 % FS/°C
<±0,06 % FS/°C
(not galvanically
tage
8
V
[
]
0,02
A
.
CE1N1919en01
2019-10-09

Advertisement

loading

This manual is also suitable for: