LG ZBNQ09GL1A0 Engineering Product Data Book page 94

Table of Contents

Advertisement

Single Free Combination
8. ZUUQ18GA0 [ZUAB1] + ZBNQ18GM1A0 [ZBNQ18GM1A0]
8.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
Obstacle on the Suction side
Re
To
Tf
Re
Front
Case 1
To ≥ 1,000(39-3/8)
Re ≥ 100(3-15/16)
Tf ≤ 500(19-11/16)
Case 2
Re ≥ 300(11-13/16)
Obstacle on the Discharge side
Front
Front
Ft
Ft
To ≥ 1,000(39-3/8)
Tr ≤ 500(19-11/16)
Obstacle on the Suction and Discharge side
Ld >H (Ls should be lower H.)
※ Close the bottom of the installation frame
to prevent the discharged
air from being bypassed
Front
Ft
Re
Front
To ≥ 1,000(39-3/8)
Tf ≤ 500(19-11/16)
Ld ≤ H
Ft
Re
Front
Front
Collective/Continuous Installation
(Multiple Columns)
Front
Front
Ft
Fb
Rb
※ In case of Multiple columns/continuous installation,
Ls should be lower than H.
Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
Lt
Front
Case 1
Re ≥ 100(3-15/16)
Lt ≥ 100(3-15/16)
Rt ≥ 100(3-15/16)
※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt
To
Tr
Case 1
Ft ≥ 500(19-11/16)
To
Tr
Ft
Re
Case 1
Ft ≥ 500(19-11/16)
Re ≥ 300(11-13/16)
Case 1
To
Tf
Ft ≥ 500(19-11/16)
Re ≥ 300(11-13/16)
Ft
Re
To ≥ 1,000(39-3/8)
Tf ≤ 500(19-11/16)
Front
Re
※ Case 1 : No obstacle on top side
Case 2 : Obstacle on top side
Re
Rt
Front
Case 2
Re ≥ 300(11-13/16)
Lt ≥ 150(5-29/32)
Rt ≥ 150(5-29/32)
300(11-13/16) and Rt,Bw,Rb
Front
Ft
Case 2
Ft ≥ 500(19-11/16)
Re
Front
Ft
Case 2
Ft ≥ 1,000(39-3/8) *
Re ≥ 300(11-13/16)
* If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Case 2
Ft ≥ 1,000(39-3/8)
Re ≥ 300(11-13/16)
Ft
Rb
Fb
Front
Front
Ft
Rb
Fb
Front
Front
Bw
8-6
Product Data
[Unit : mm(inch)]
Re
Bw
Lt
Front
Front
Case 1
Case 2
Re ≥ 300(11-13/16)
Re ≥ 300(11-13/16)
Lt ≥ 1,000(39-3/8)
Lt ≥ 1,000(39-3/8)
Rt ≥ 200(7-7/8)
Rt ≥ 200(7-7/8)
Bw ≥ 100(3-15/16)
Bw ≥ 100(3-15/16)
600(23-5/8) for ALL CASE.
Bw
Front
Front
Ft
Case 1
Case 2
Ft ≥ 1,000(39-3/8)
Ft ≥ 1,000(39-3/8)
Bw ≥ 100(3-15/16)
Bw ≥ 100(3-15/16)
Re
Bw
Front
Front
Case 1
Case 2
Ft ≥ 1,000(39-3/8)
Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16)
Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Bw ≥ 100(3-15/16)
Case 1
Case 2
Ft ≥ 1,500(59-1/16)
Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16)
Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Bw ≥ 100(3-15/16)
※ In case of series installation (2 Units or more)
for 2 Fan models, Ld should be lower than H/2.
Re
1 Column
Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Fb ≥ 2,000(78-3/4)
Front
Re ≥ 100(3-15/16)
Re
Multiple Columns
Ft ≥ 1,500(59-1/16)
Front
Rb ≥ 600(23-5/8)
Fb ≥ 3,000(118-1/8)
Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Rt