LG ZBNQ09GL1A0 Engineering Product Data Book page 146

Table of Contents

Advertisement

Single Free Combination
Product Data
12. ZUUQ24GA0 [ZUAC1] + ZTNQ24GTLA0 [ZTNQ24GTLA0]
12.8 Capacity Correction Factor
Capacity correction factor (%) by Equivalent pipe length (m)
Operation
5
7.5
10
15
20
25
30
35
40
45
50
Cooling
100.0
100.0
99.6
98.8
98.0
97.2
96.4
95.6
94.8
94.0
93.2
Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping
12-10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents