LG ZBNQ09GL1A0 Engineering Product Data Book page 86

Table of Contents

Advertisement

Single Free Combination
Product Data
7. ZUUQ18GA0 [ZUAB1] + ZTNQ24GNLE0 [ZTNQ24GNLE0]
7.8 Capacity Correction Factor
Capacity correction factor (%) by Equivalent pipe length (m)
Operation
5
7.5
10
15
20
25
30
35
40
45
50
Cooling
100.0
100.0
99.6
98.8
98.0
97.2
96.4
-
-
-
-
Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping
7-10