Microtech Unit Controller Inputs/Outputs - Daikin NAVIGATOR WWV Installation Operation & Maintenance

Water-cooled screw chillers
Hide thumbs Also See for NAVIGATOR WWV:
Table of Contents

Advertisement

OPERATION
MicroTech Unit Controller Inputs/
Outputs
Figure 21: Analog Inputs
#
Description
AI1
Evap Entering Water Temp
Condenser Entering Water
AI2
Temp
X3
Demand Limit
X4
LWT Reset
X6
Evap Leaving Water Temp
Table 8: Analog Outputs
#
Description
X5
Cooling Tower VFD Speed
X7
Cooling Tower Bypass Valve Position
Table 9: Digital Inputs
#
Description
Unit Ground Fault
DI1
Relay
Evaporator Flow
DI2
Switch
Oil Presence
DI3
Sensor
DI4
Remote Switch
DI5
Unit Switch
DI6
External Alarm
X1
Emergency Stop
X2
Mode Switch
Condenser Flow
X8
Switch
Table 10: Digital Outputs
#
Description
DO1
Evaporator Water Pump 1
DO2
Alarm Relay
DO3
Condenser Water Pump 1
DO5
Cooling Tower Fan 1
DO6
Cooling Tower Fan 2
DO9
Evaporator Water Pump 2
DO10
Condenser Water Pump 2
DAIKIN APPLIED
Signal Source
NTC 10KThermister
NTC 10KThermister
4-20 mA Current
4-20 mA Current
NTC 10KThermister
Output Signal
0-10VDC
0-10VDC
Signal Off
Signal On
Fault
No Fault
No Flow
Flow
Oil Not Present
Oil Present
Unit disable
Unit enable
Unit disable
Unit enable
Unit disable
Unit enable
Unit off
Unit enable
Cool Mode
Ice Mode
No Flow
Flow
Output OFF
Output ON
Pump Off
Pump On
Alarm not
Alarm Active
Active
Pump Off
Pump On
Off
On
Off
On
Pump Off
Pump On
Pump Off
Pump On
CC1 Module
Table 11: Analog Inputs
#
Description
X1
Discharge Temperature
X2
Evaporator Pressure
X3
Oil Pressure
X4
Condenser Pressure
X6
Condenser Leaving Water Temp
Table 12: Digital Outputs
#
Description
Oil Return Solenoid
DO1
Valve & Jet Pump Sole-
noid Valve
DO3
VVR SV 1
DO4
VVR SV 2
DO5
VVR SV 3
Evaporator EXV1 Module
Table 13: Analog Inputs
#
Description
X2
Suction Temperature
X3
Liquid Temperature
Table 14: Stepper Motor Output
#
Description
M1+
Evaporator EXV Stepper Coil 1
M1-
M2+
Evaporator EXV Stepper Coil 2
M2-
RapidRestore Module
Table 15: Digital Inputs
#
Description
RapidRestore
DI1
Enable
Compressor VFD1 Module
Table 16: Digital Inputs
#
Description
Mechanical High
37
Press Switch
Table 17: Analog Inputs
#
Description
54
Motor Temperature
26
Signal Source
NTC 10k Thermister
Ratiometric 0.5-4.5 Vdc
Ratiometric 0.5-4.5 Vdc
Ratiometric 0.5-4.5 Vdc
NTC 10k Thermister
Output Off
Output On
Solenoid Closed
Solenoid Open
Solenoid Closed
Solenoid Open
Solenoid Closed
Solenoid Open
Solenoid Closed
Solenoid Open
Signal Source
NTC 10k Thermister
NTC 10k Thermister
Signal Off
Signal On
Disable
Enable
Signal Off
Signal On
Safe Torque Off
Normal Operation
Signal Source
PTC Thermister
NAVIGATOR WWV/TWV

Advertisement

Table of Contents
loading

This manual is also suitable for:

Navigator twv

Table of Contents