Condensate Drain Lines & Drain Trap - Amana CVC96 Installation Instructions Manual

Two-stage gas furnace
Hide thumbs Also See for CVC96:
Table of Contents

Advertisement

1. Detailed instructions for the installation of the venting
system design or the venting system components;
and
2. A complete parts list for the venting system design or
venting system.
d. MANUFACTURER REQUIREMENTS - GAS
EQUIPMENT VENTING SYSTEM NOT
PROVIDED. When the manufacturer of a
Product Approved side wall horizontally
vented gas fueled equipment does not
provide the parts for venting the flue gases,
but identifies "special venting systems", the
following requirements shall be satisfied by the
manufacturer:
1. The referenced "special venting system" instructions
shall be included with the appliance or equipment
installation instructions; and
2. The "special venting systems" shall be Product
Approved by the Board, and the instructions for
that system shall include a parts list and detailed
installation instructions.
e. A copy of all installation instructions for all
Product Approved side wall horizontally vented
gas fueled equipment, all venting instructions,
all parts lists for venting instructions, and/or all
venting design instructions shall remain with the
appliance or equipment at the completion of the
installation.
#1
#4
#7
#9
NOTE: Drain components shown for information
purposes only. For horizontal installations, a
Horizontal Drain Kit may be needed. Refer to the
Specifications Sheet for kit part number.
#2
#5
#8
#10
Coupling
100 Degree
#11
Elbow
Figure 25
CONDENSATE DRAIN LINES & DRAIN
A condensing gas furnace achieves its high level
of efficiency by extracting heat from the products of
combustion to the point where condensation takes place.
The condensate must be collected in the furnace drain trap
and routed to an appropriate drain location in compliance
with local and national codes.
Follow the bullets listed below when installing the drain
system. Refer to the following sections for specific details
concerning furnace drain trap installation and drain hose
hook ups.
• The drain trap supplied with the furnace must be
used.
• The drain trap must be primed at time of installation.
• The drain line between furnace and drain location
must meet local and nation codes.
• The drain line between furnace and drain location
must maintain a 1/4 inch per foot downward slope
toward the drain.
• Do not trap the drain line in any other location than at
the drain trap supplied with the furnace.
• If the drain line is routed through an area which may
see temperatures near or below freezing, precautions
must be taken to prevent condensate from freezing
within the drain line.
• If an air conditioning coil is installed with the furnace,
a common drain may be used. An open tee must be
installed in the drain line, near the cooling coil, to
relieve positive air pressure from the coil's plenum.
This is necessary to prohibit any interference with the
function of the furnace's drain trap.
NOTE: In vertical installations, air conditioning
coil condensate may drain into the furnace trap
as long as there is a trap between the coil and the
furnace trap and the drain pipe is not terminating
below the water level of the furnace trap.
General Drain Information
All furnace models come with a factory installed drain trap.
For vertical installations, the trap will remain in the factory
position except for a counterflow when the installer desires
the drain to exit the right side. All furnace models installed
horizontally require the trap to be relocated. Many drain
hoses have a built–in grommet which will provide a cabinet
seal when installed. See instructions below for your model
and installation position.
NOTE: Both sides of the drain trap must be primed
prior to initial furnace start up
Field Supplied Drain
Drain the furnace and air conditioning coil if applicable,
in compliance with code requirements. In horizontal or
counterflow installations, a field installed rubber coupling
will allow the drain trap to be removed for cleaning. The